Endress+Hauser Liquicap M FTI51 Operating Instructions Manual page 44

Capacitance point level switch for liquids
Hide thumbs Also See for Liquicap M FTI51:
Table of Contents

Advertisement

Commissioning
44
4 →
7
3
-
+
5
> 2 s
A0042822
Press the  key > 2 s.
Full calibration
Make sure that the probe is covered by the medium up to the desired switch-point.
Carrying out full calibration
1 →
7
3
-
+
5
> 2 s
A0043261
Press the  key > 2 s.
4 →
2
1
7
3
-
+
5
A0042461
Set the function switch to
position 1.
5 →
7
3
-
+
5
A0042459
Release the  key when the
green LED 1 starts to flash.
2 →
7
3
-
+
5
A0043262
Release the  key when the
green LED 5 starts to flash.
5
7
3
-
+
5
A0043637
Liquicap M FTI51
6
7
3
-
+
5
A0043260
The process of saving the
empty calibration is finished
when the green LED 1 lits.
3 →
7
3
-
+
5
A0043263
The process of saving the full
calibration is complete when
the green LED 5 lights up.
Endress+Hauser