Installation Instructions - Endress+Hauser Liquicap M FTI51 Operating Instructions Manual

Capacitance point level switch for liquids
Hide thumbs Also See for Liquicap M FTI51:
Table of Contents

Advertisement

Liquicap M FTI51
Endress+Hauser
4 →
A0042114
Pull out the cable with the
cone.
7 →
A0042549
Remove the blade plug from
the socket.
 14
Cable connections
1
External screening (not required)
2
Strand black (bk) (not required)
3
Coaxial cable with central core a screening
4
Solder the red (rd) strand with the central core of the coaxial cable (probe)
5
Solder the strand with the screening of the yellow (ye) coaxial cable (ground)
6
Strand yellow and green (gn/ye) with a ring terminal
4.5

Installation instructions

NOTICE
Do not damage the probe insulation during installation!
Check the rod insulation.
5 →
1.
34
2.
A0042115
Remove the seal and loosen
the adapter disk with the
open-end wrench AF34.
8 →
A0042546
Loosen the screw to disconnect
the yellow-green cable.
1
bk
2
3
6
4
5
gn/ye
rd
ye
Mounting
6 →
1.
2.
A0042548
Remove the snap ring with a
snap ring pliers and cut the
yellow cable.
9
A0042119
Loosen the nut (M4) of the
blade plug.
A0042547
21