Carrying Out Empty Calibration - Endress+Hauser Liquicap M FTI51 Operating Instructions Manual

Capacitance point level switch for liquids
Hide thumbs Also See for Liquicap M FTI51:
Table of Contents

Advertisement

Liquicap M FTI51
Endress+Hauser
To set the range to 0 to 1 600 pF:
1 →
7
3
-
+
5
A0042452
4 →
7
3
-
+
5
> 2 s
A0042454
Press the  key > 2 s.
7
7
3
-
+
5
A0043270
7.2.2

Carrying out empty calibration

The empty calibration stores the capacitance value of the probe when the tank is
empty. If the measured capacitance value is, for example, 50 pF (empty calibration), a
switching threshold of 2 pF is added to this value. In this case, the capacitance value
of the switch-point would be 52 pF.
The switching threshold depends on the value set for the switch-point adjustment
→  46.
Carrying out empty calibration
Make sure that the probe is not covered with the product.
2 →
1
4
7
3
-
+
5
A0042453
Set the function switch to
position 4.
5 →
7
3
-
+
5
A0042455
Commissioning
3 →
7
3
-
+
5
A0043663
6 →
4
2
7
3
-
+
5
A0042456
Set the function switch to
position 2.
41