Protecting Settings From Unauthorized Access; Locking Or Unlocking The Hardware; Locking Or Unlocking The Display Operation; Parameter Configuration - Locking Or Enabling - Endress+Hauser Liquiphant FTL51B Operating Instructions Manual

Vibronic hart point level switch for liquids
Hide thumbs Also See for Liquiphant FTL51B:
Table of Contents

Advertisement

Liquiphant FTL51B HART
Endress+Hauser
Navigation: Diagnostics → Simulation → Simulation
9.9

Protecting settings from unauthorized access

9.9.1

Locking or unlocking the hardware

 25
Functions of the DIP switches on the electronic insert
1
DIP switch for safety function, software-defined (SW, default=MAX) or set permanently to MIN
2
DIP switch for locking and unlocking the device (hardware)
DIP switch (2) on the electronic insert is used to lock or unlock operation.
• If operation is locked via the DIP switch, you can only unlock operation again via the
DIP switch.
• If operation is locked via the operating menu, you can only unlock operation again
via the operating menu.
• If operation is locked via the DIP switch, the lock icon  appears on the local
display.
9.9.2

Locking or unlocking the display operation

Lock or unlock display operation:
1. Press the  key for at least 2 s.
 A dialog box appears.
2. Lock or unlock display operation.
Display operation locks automatically (except in the SIL wizard):
• After 1 minute on the main page if no key has been pressed
• After 10 minutes within the operating menu if no key has been pressed
9.9.3

Parameter configuration - locking or enabling

If operation is locked by means of the DIP switch, you can only unlock operation again
by means of the DIP switch.
Software - via password in FieldCare, DeviceCare, SmartBlue app
As-delivered state:
The user role is set to Maintenance when the device is delivered to the customer.
Parameter configuration (Maintenance user role):
The device can be fully configured with the Maintenance user role.
Locking access:
After configuring with the Maintenance user role, access can be locked by assigning a
password. The lock changes the Maintenance user role to the Operator user role.
Display
2
1
Commissioning
A0046569
35