Setting the MIN, MAX and SIL fail-safe mode
The SIL mode function is only available in conjunction with electronic insert FEI55.
By selecting the fail-safe mode correctly, you ensure that the output always operates
safely with the quiescent current.
Minimum fail-safe mode (MIN)
The output switches if the switch-point is undershot (probe uncovered), a fault occurs or
the line voltage fails.
Maximum fail-safe mode (MAX)
The output switches if the switch-point is exceeded (probe covered), a fault occurs or the
line voltage fails.
Setting the MIN fail-safe mode:
The factory setting is set to MAX fail-safe mode.
1 →
7
3
-
+
5
A0042483
4 →
7
3
-
+
5
> 2 s
A0042493
Press the  key > 2 s to set
the MIN fail-safe mode.
7
7
3
-
+
5
A0042483
2 →
1
7
7
3
-
+
5
A0042492
Set the function switch to
position 7.
5 →
7
3
-
+
5
A0043657
The MIN fail-safe mode is set.
Liquicap M FTI51
3 →
7
3
-
+
5
A0042496
The green LED 5 shows the
factory setting.
6 →
7
1
7
3
-
+
5
A0042649
Set the function switch to