Shortening The Connecting Cable - Endress+Hauser Liquicap M FTI51 Operating Instructions Manual

Capacitance point level switch for liquids
Hide thumbs Also See for Liquicap M FTI51:
Table of Contents

Advertisement

Liquicap M FTI51
Endress+Hauser
4.4.5

Shortening the connecting cable

NOTICE
Risk of damage to connections and cable.
Make sure that neither the connecting cable nor the probe is turning with the pressing
screw!
• The maximum total length of the rod L1 and the cable L4 is 10 m (33 ft).
• The maximum connection length between the probe and the separate housing is
6 m (20 ft).
• When ordering a device with separate housing, the desired length must be
specified.
• We recommend reusing all strands with ring terminals in case of shortening the
connecting cable.
• To avoid the risk of short-circuiting when the strands are not reused, the
connections of the new ring terminals fittings must be isolated with a heat
shrinking sleeve.
• Use heat-shrink tubes to insulate all soldered joints.
If the cable connection has to be shortened or led through a wall, it must be separated
from the process connection.
Probe without active buildup compensation
Disconnecting the connection cable
1 →
22
A0042111
Loosen the pressing screw with
an open-end wrench AF22.
4 →
A0042114
Pull out the cable with the
cone.
2 →
A0042112
Pull the insert seal out of the
cable gland.
5 →
1.
34
2.
A0042115
Remove the seal and loosen
the adapter disk with the
open-end wrench AF34.
Mounting
3 →
22
34
A0042113
Block the adapter disk with the
open-end wrench AF34 and
loosen the cable gland with the
open-end wrench AF22.
6 →
A0042545
Remove the snap ring with a
snap ring pliers.
19