Endress+Hauser Liquicap M FTI51 Operating Instructions Manual page 64

Capacitance point level switch for liquids
Hide thumbs Also See for Liquicap M FTI51:
Table of Contents

Advertisement

Commissioning
64
 48
The probe is covered during calibration
Make sure that the probe is not covered with product.
Carrying out empty calibration
1 →
-
+
A0042514
4 →
2x
-
+
A0042517
The green LED 1 flashes
quickly to indicate that the
value has been saved correctly.
Make sure that the probe is is covered by the medium up to the desired switch-point.
2 →
-
+
A0042515
Make sure that the calibration
DIP switch is in position
"Uncovered".
5
1x
-
+
A0042518
The process of saving the
empty calibration value is
finished when the green LED 1
flashes slowly.
Liquicap M FTI51
A0042404
3 →
-
+
> 2 s
A0042516
Press the A and B keys > 2 s.
Endress+Hauser

Advertisement

Table of Contents
loading

Table of Contents