Operation
5.1.6 Basic settings
Function
Function
group
BASE
DISP
Basic
settings
UNIT
TAU
DESI
5.1.7 Calibration
Function
Function
group
CAL
HIF
Calibration
LOWF
20
Settings
Display
PV
PVRO
TMP
TMPR
OFF
OFFR
Technical
×C
unit
×F
Damping
0.0
DESINA
NO
Only for 2 x
YES
PNP switch
outputs
Settings
Learn High
RUN
Flow
WAIT
Learn Low
RUN
Flow
WAIT
Description
PV: displays the current measured value
PVRO: displays the current measured value rotated
180°
TMP: displays the current medium temperature
TMPR: displays the current medium temperature
rotated 180°
OFF: display off
OFFR: display off, rotated 180°
Factory setting: current measured value (PV)
Display medium temperature unit °C or °F
Factory setting: °C
Only visible if the current medium
temperature TMP is selected in the DISP
mode.
Measured value damping with regard to display
value and output: 0 (no damping) or 9 to 40 s (in
increments of 1 second)
Factory setting: 0 s
Behavior as per DESINA: PIN assignment of the M12
connector is in accordance with the guidelines of
DESINA
(DESINA = DistributEd and Standardized
INstAllation technology for machine tools and
manufacturing systems)
Factory setting: NO
Description
RUN, WAIT: setting for the maximum flow rate
occurring. 100% value (→ Page 16)
RUN, WAIT: setting for the minimum flow rate
occurring. 0% value (→ Page 16)
DTT31, DTT35
Endress+Hauser