Commissioning
42
To carry out an empty calibration, set the measuring range first → 40.
1 →
7
3
-
+
5
A0042458
4 →
7
3
-
+
5
A0042460
‣
The process of saving the
empty calibration is finished.
The green LED 1 lits.
7.2.3
Carrying out full calibration
The full calibration measures the capacitance value of the probe when the tank is full.
If the measured capacitance value is, for example, 100 pF (full calibration), a
switching threshold of 2 pF is subtracted from this value. The capacitance value of the
switch-point is thus 98 pF.
The switching threshold depends on the value set for the switch-point adjustment
→ 46.
Make sure that the probe is covered by the medium up to the desired switch-point.
To carrying out full calibration
1 →
7
3
-
+
5
A0042452
2 →
7
3
-
+
5
> 2 s
A0042821
‣
Press the key > 2 s.
5 →
2
1
7
3
-
+
5
A0042647
‣
Set the function switch to
position 1.
2 →
1
2
7
3
-
+
5
A0042457
‣
Set the function switch to
position 2.
Liquicap M FTI51
3 →
7
3
-
+
5
A0042459
‣
Release the key when the
green LED 1 starts to flash.
6
7
3
-
+
5
A0043647
3 →
7
3
-
+
5
A0043650
Endress+Hauser