Mounting

10
4
Mounting
4.1

Mounting requirements

4.1.1

Mounting the sensor

The Liquicap M FTI51 can be installed from the top or the bottom or from the side.
Make sure that:
• the probe is not installed in the area of the filling curtain
• the probe is not in contact with the container wall
• the distance from the container floor is ≥10 mm (0.39 in)
• multiple probes are mounted next to each other at the minimum distance between
the probes of 500 mm (19.7 in)
• the probe is at a sufficient distance from the agitator if using the probe in agitator
tanks
• the rod probes with a ground tube are used in the event of severe lateral load
≥500 (19.7)
MAX
MIN
 1
Mounting the sensor in electrically conductive tanks. Unit of measurement mm (in)
MAX
MIN
Liquicap M FTI51
A0042377