Start-Up - Burkert 8792 Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

21

START-UP

Before start-up, carry out fluid and electrical installation of Type 8792/8793 and of the valve. For
description see Chapter "13", "14" and "15".
When the operating voltage is applied, Type 8792/8793 is operating and is in the AUTOMATIC operating
state. The display shows the process level with the values for POS and CMD.
The following basic settings must be made for starting up the device:
Device
Sequence Type of basic setting
type
8792 and
8793
only 8793
(Process
controller)
Table 33: Start-up sequence
The basic settings are made on the setting level.
To switch from the process to the setting level, press the
Then the main menu (MAIN) of the setting level is indicated on the display.
WARNING!
Risk of injury from improper operation.
Improper operation may result in injuries as well as damage to the device and the area around it
▶ Before start-up, ensure that the operating personnel are familiar with and completely understand the
contents of the operating instructions.
▶ Observe the safety instructions and intended use.
▶ Only adequately trained personnel may start up the equipment/the device.
74
Basic setting of the device:
1
Set input signal
(standard signal).
2
Adjust device to the local
conditions.
3
Activate process controller.
Basic setting of the process
controller:
4
– Setting the hardware
– Parameter setting of the
5
software.
Automatic linearization of
6
the process characteristics.
Automatic parameter setting
7
for the process controller.
english
Type 8792, 8793
Type 8792, 8793
Start-up
Setting via
Description
in chapter
INPUT
"23.1"
X.TUNE
"23.2"
ADD.FUNCTION
"24"
P.CONTROL
"25"
→ SETUP
"25.2"
→ PID.PARAMETER "25.3"
P.Q'LIN
"25.4"
P.TUNE
"25.5"
MENU
key for approx. 3 seconds.
Requirement
essential
essential
to be
imple-
mented
optionally