If several diagnosis messages are available with different status signals, the status signal with the highest
priority is shown on the display.
Overview of the status signals according to NE 107 (NE = NAMUR recommendation):
Priority
Status signal
Description
Table 79: CONFIG.MSG; overview of status signals
The following status signals have been preset at the factory for the messages of the diagnosis functions:
Diagnosis function
SERVICE.TIME
TRAVEL.ACCU
CYCLE.COUNTER
TEMP.CHECK
STROKE.CHECK
PV.MONITOR
POS.MONITOR
Table 80: CONFIG.MSG; factory setting (Default)
Assignment of status signals:
Key
Action
/
Select CONFIG.MSG
ENTER
Press
/
Select required diagnosis
function
ENTER
Press
/
Select required status signal
SELEC
Press
EXIT
Press
EXIT
Press
Table 81: CONFIG.MSG; assignment of status signals
148
1
2
Failure
Function check
Status signal according to NE 107
Maintenance required
Maintenance required
Maintenance required
Out of specification
Out of specification
Out of specification
Out of specification
Description
All activated diagnosis functions, which can output a message,
are displayed.
The list of possible status signals is displayed.
The selected status signal is now marked by a filled circle
Acknowledgment and simultaneous return to the CONFIG.MSG
menu.
The status signal is now assigned to the diagnosis function.
Return to the DIAGNOSE main menu.
english
Type 8792, 8793
Type 8792, 8793
Configuring the auxiliary functions
3
4
Out of specification
Maintenance
required
Signal
Miniature
Priority
4
4
4
3
3
3
3
.