Type 8792, 8793
Type 8792, 8793
Configuring the auxiliary functions
25.2.14.3. Setting of the submenu options of OUT BIN 1 / OUT BIN 2
Key
Action
MENU
Press
/
Select OUTPUT
ENTER
/
Select OUT BIN1/2
ENTER
Press
Table 59: OUT BIN1 / OUT BIN2; opening the submenu
• POS.Dev - Alarm output for excessively large control deviation of the positioner
• POS.Lim-1/2 - Output of the current position with respect to a specified limit position
Key
Action
POS.Dev - Alarm output for excessively large control deviation of the positioner:
/
Select POS.Dev
SELEC
Press
/
Increase value
Reduce value
OK
Press
POS.Lim-1/2 - Output of the current position with respect to a specified limit position:
/
Select POS.Lim-1/2
SELEC
Press
/
Increase value
Reduce value
OK
Press
Table 60: OUT BIN1 / OUT BIN2; setting value for POS.Dev or POS.Lim-1/2
Description
Switching from process level
for approx. 3 s
(To do this, the auxiliary function must be incorporated into the
main menu).
The outputs are displayed.
Submenu options of OUT BIN 1/2 are displayed.
Description
The input screen for the limit value (Deviation:) is opened.
Input limit value for permitted control deviation.
Adjustment range: 1...50 % (must not be less than the dead
band).
Acknowledgment and simultaneous return to the OUT BIN 1/2
menu.
Then set the required switching status in the OUT.type submenu.
The input screen for the limit position (Limit:) is opened.
Input limit position.
Adjustment range: 0...100 %.
Acknowledgment and simultaneous return to the OUT BIN 1/2
menu.
Then set the required switching status in the OUT.type submenu.
setting level.
english
125