X1 - M12, 8-Pole Circular Connector; X2/X3 - M12, 5-Pole Socket/Circular Connector - Bus Connection - Burkert 8792 Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

27.7.3

X1 - M12, 8-pole circular connector

Pin
Configuration
1
not used
2
not used
Operating voltage
3
GND
4
+24 V
Input signals of the control centre (e.g. PLC)
5
Binary input +
6
Binary input –
Output signals to the control centre (e.g. PLC) - (only used for binary output option)
7
Binary output 1 (referring to Pin 3)
8
Binary output 2 (referring to Pin 3)
Table 102: Pin assignment; X1 - M12, 8-pole circular connector; PROFIBUS DP
27.7.4
X2/X3 - M12, 5-pole socket/circular connector - bus
connection
Pin
Configuration
1
VP+5
2
RxD/TxD-N
3
DGND
4
RxD/TxD-P
5
Shielding
Table 103: Pin assignment; X2/X3 - M12, 5-pole circular connector/socket - bus connection, PROFIBUS DP
188
english
Type 8792, 8793
Type 8792, 8793
Operating structure and factory settings
On the device
External circuit / Signal level
side
3
24 V DC ± 10%
max. residual ripple 10%
4
5
+
6
GND (identical with Pin 3)
7
0 – 24 V
8
0 – 24 V
External circuit / Signal level
Supply the terminating resistors
Received/transmitted data -N, A-line
Data transmission potential (earth to 5 V)
Received/transmitted data -P, B-line
Shielding / protective earth
0 – 5 V
(log. 0)
10 – 30 V (log. 1)

Advertisement

Table of Contents
loading

This manual is also suitable for:

8793

Table of Contents