Configuring the auxiliary functions
Key
Action
OK
Press
EXIT
Press
EXIT
Press
Table 93: STROKE.CHECK; end position monitor.
POS.MONITOR –Position monitoring
The POS.MONITOR function monitors the current position of the actuator.
The tolerance band for the set-point value is specified in the DEADBAND submenu.
A period for alignment of the actual value with the set-point value is specified in the COMP.TIME submenu
(compensation time).
The compensation time COMP.TIME starts recording as soon as the set-point value is constant. When the
compensation time has elapsed, monitoring starts.
If the control deviation (DEV) of the actual value is greater than the tolerance band of the set-point value
during monitoring, a message is output.
• To do this, a history entry is made in the HISTORY submenu. For description see "26.2.22.7. History
entries in the HISTORY submenu".
• The status signal, which is assigned to the message, is indicated at short intervals on the display.
See also D.MSG and CONFIG.MSG in Chapter "26.2.22.5", page 147.
Display POS.MONITOR
POS:MONITOR
2.0 %
DEADBAND
COMP.TIME
10.0 sec
HISTORY
EXIT
29-11-1
INPUT
Table 94: POS.MONITOR; position monitor
Schematic representation
1.4
1.2
CMD
1
0.8
POS
0.6
0.4
0.2
0
0
1
2
3
4
COMP.TIME
Fig. 97:
POS.MONITOR; schematic representation of position monitor
Description
Acknowledge value.
Return to the STROKE.CHECK menu.
Return to the DIAGNOSE main menu.
Description of the functions
The tolerance band of the set-point value preset at the factory to 2 %
can be changed in the DEADBAND submenu.
The compensation time is set in COMP.TIME (compensation time).
The history entries of the last 3 messages can be viewed and deleted
in the HISTORY submenu.
DEV
5
6
7
8
9
10
Key:
DEADBAND = adjustable tolerance
DEADBAND
band as %.
COMP.TIME = adjustable time
in seconds expected until the
control deviation is compared with
the tolerance band.
DEV = control deviation
english
161