7

WIRING CONNECTION

HGM9560 controller's rear as following:
NO.
Functions
1
DC input B-
2
DC input B+
3
COM Output 7,8
Aux. output 7
4
Aux. output 8
5
Aux. output 1
6
Aux. output 2
7
Aux. output 3
8
9
Reserved
Aux. input 1
10
Aux. input 2
11
Aux. input 3
12
HGM9560 Bus Tie Mains Parallel Unit
Fig.2 Controller Back Panel
Table 11 Description of Terminal Connection
Cable Size
2
2.5mm
Connected with negative of starter battery.
Connected with positive of starter battery. If wire length
2.5mm
2
is over 30m, better to double wires in parallel. Max. 20A
fuse is recommended.
2.5mm
2
Connected with B+.
2
1.5mm
B+ is supplied by 3 point, rated 16A.
2
1.5mm
B+ is supplied by 3 point, rated 16A.
B+ is supplied by 2 point, rated
1.5mm
2
7A.
B+ is supplied by 2 point, rated
1.5mm
2
7A.
B+ is supplied by 2 point, rated
1.5mm
2
7A.
/
This is reserved terminals, do not connect to wire.
Ground connected is active
1.0mm
2
(B-)
Ground connected is active
1.0mm
2
(B-)
Ground connected is active
2
1.0mm
(B-)
Remark
Details see form 2.
Details see form 3.