Smartgen HGM9560 User Manual page 25

Bus tie mains parallel unit
Hide thumbs Also See for HGM9560:
Table of Contents

Advertisement

No.
Items
2
Over Voltage
3
Under Voltage
4
Over Frequency
5
Under Frequency
6
ROCOF
7
Vector Shift
Timer Setting
1
Start Delay
2
Stop Delay
Battery Setting
1
Rated Voltage
2
Over Voltage
3
Under Voltage
Bus Setting
1
AC System
2
Rated Voltage
3
Rated Frequency
4
Volt. Trans.(PT)
5
Bus Rated (kW)
6
Bus Rated (kVar)
7
Load Ramp Rate
8
Load Ramp Point
9
Load Ramp Delay
HGM9560 Bus Tie Mains Parallel Unit
Parameters
Defaults
(0-200)%
105%
(0-200)%
95%
(0-200)%
105%
(0-200)%
95%
(0-1.00)Hz/s
0.20
(0-20.0)°
6.0
(0~3600)s
5
(0~3600)s
30
(0-60.0)V
24.0
(0-200)%
120%
(0-200)%
85%
(0~3)
0
(30~30000)V
230
(10.0-600.0) Hz
50.0
(0-1)
0
(1-20000)kW
276
(1-20000)kvar
210
(0.1-100.0)%
3.0
(0.1-40.0)%
10.0
(0-30)s
0
Description
alarm occurs, mains breaker will open and
warning alarm will be initiated.
Setting value is mains rated voltage's
percentage, action (default: trip and stop)
and delay value (default: 0.1s) can be set.
Setting value is mains rated frequency's
percentage, action (default: trip and stop)
and delay value (default: 0.1s) can be set.
Setting value is rate of change of frequency
(ROCOF), action (default: trip and stop) and
delay value (default: 0.1s) can be set.
Setting value is the change value of voltage
waveform, action (default: trip and stop) and
delay value (default: 0.1s) can be set.
Time from mains abnormal or remote start
signal is active to start genset.
Time from mains normal or remote start
signal is inactive to stop genset.
Standard for checking battery over/under
voltage.
Setting value is mains rated voltage's
percentage, return value (default: 115%) and
delay value (default: 60s) can be set.
Setting value is mains rated voltage's
percentage, return value (default: 90%) and
delay value (default: 60s) can be set.
0: 3P4W; 1: 3P3W;
2: 2P3W; 3: 1P2W.
To offer standards for detecting of bus'
over/under voltage. (It is primary voltage
when using voltage transformer; it is line
voltage when AC system is 3P3W while it is
phase voltage when using other AC system).
To
offer
standards
over/under frequency.
0: Disable;
1:Enable
The primary secondary voltages can be set.
Bus' active power, used for load distributes.
Bus'
reactive
power,
distributes.
Speed rate(%/s) of genset upload/unload
Each "Load Ramp Point" unit value increases,
the load will added after "Load Ramp Delay".
for
detecting
of
used
for
load
Page 25 of 47