Smartgen HGM9560 User Manual page 29

Bus tie mains parallel unit
Hide thumbs Also See for HGM9560:
Table of Contents

Advertisement

No.
Items
2
MSC Priority
3
Sync Freq. Gain
4
Sync Freq. Stability
5
Sync Volt. Gain
6
Sync Volt. Stability
7
kW Control Gain
8
kW Control Stability
9
kvar Control Gain
10
kvar Control Stability
11
Dead Bus Volt
12
Slip Frequency
13
Voltage Difference
Positive
14
Difference
Negative
15
Difference
Phase
16
Difference
17
Fail to Sync Delay
18
Fail to Sync Action
19
MSC Number
20
Comm. Alarm Action
21
Comm. Ratio
22
Scheduled Run PCT
HGM9560 Bus Tie Mains Parallel Unit
Parameters
(0-31)
(0-500)
(0-2000)
(0-500)
(0-2000)
(0-500)
(0-2000)
(0-500)
(0-2000)
(10-50)V
(0-1.00)Hz
(0-30)V
Freq
(0-2.0)Hz
Freq
(0-2.0)Hz
Angle
(0-20)°
(5.0-300.0)s
(0-1)
(1-32)
(0~2)
(0~3)
(0-100)%
Defaults
internet. All the MSC ID should be unique.
0
Smaller values represent higher priorities.
20
Adjust and control before paralleling.
20
Adjust and control before paralleling.
20
Adjust and control after paralleling.
20
Adjust and control after paralleling.
20
Adjust and control before paralleling.
20
Adjust and control before paralleling.
20
Adjust and control before paralleling.
20
Adjust and control before paralleling.
It is considered Bus no power when Bus
30
voltage is lower than dead Bus voltage.
Adjust bus frequency and enable it greater
than mains frequency.
When slip frequency is 0:
If the frequency difference is greater than
0.10
0.1Hz,
synchronized;
If the frequency difference is smaller than
0.1Hz, then the phase will be synchronized;
The voltage difference between bus and
mains.
3
synchronization when the voltage difference
between mains and Bus is lower than
synchronization voltage difference.
The frequency difference between bus and
0.2
mains.
synchronization
difference between mains and Bus is less
0.1
than Positive Freq Difference but more than
Negative Freq Difference.
Initial phase difference between bus and
mains. It is considered Check Phase Angle
10
when the initial phase difference is lower
than synchronization phase difference.
60.0
When the controller detects no Sync signal
during the preset delay, it will send
corresponding alarm signal according to the
action type.
0
Action Type:
0:Warn;1:Trip.
2
1
Action 0: None 1: Warn
0:500KBit/s; 1:250KBit/s;
1
2:125KBit/s; 3:50KBit/s.
80
Schedule the load value of other genset
Description
then
the
frequency
It
is
considered
It
is
considered
when
the
2: Trip
will
be
voltage
frequency
frequency
Page 29 of 47