Mains Open Operation:Press mains Open Button
1)
If mains switch didn't close, then mains open relay activate.
2)
If mains switch already closed, first of all, the controller will transfer load to bus, and only then mains open
relay activate.
Manual Stop Operation:
1)
Stop mode is selected by pressing the
confirm the operation:
a) If mains switch didn't close, then bus open relay activate.
b) If mains switch already closed, first of all, the controller will transfer load to mains, and only then bus open
relay activate.
2)
The controller will issue a stop command and the genset is in "At Rest" mode.
3)
Any available 9560 in auto mode will be issued with a stop signal. Please refer to the 9510 operating
manual for further details of the stop sequence.