Mains Control Mode - Smartgen HGM9560 User Manual

Bus tie mains parallel unit
Hide thumbs Also See for HGM9560:
Table of Contents

Advertisement

11.2

MAINS CONTROL MODE

If the power value is set as a positive number, when the mains input increases above the power setpoint, the
generator bus will supply the extra load in order to maintain the mains input at the predefined level (mains peak
lopping mode).
If the power value is set as a negative number, the generator bus will supply the preset power to mains. The
total output power of the generator bus is the sum of the consumption power and the preset power which
supplied by generator bus to mains.
Fig.4 Mains Peak Lopping Mode
HGM9560 Bus Tie Mains Parallel Unit
Page 38 of 47

Advertisement

Table of Contents
loading

Table of Contents