Ch a pt er 3 Pr o duc t S pec if ic a t io ns
 The user-defined input/output device range: X10.0~X10.15, and Y20.0~Y20.15
3_
Analog Input/Output Modules
You can assign input registers and output registers to an analog input/output module through HWCONFIG in ISPSoft.
The input registers and the output registers should be within the range between D0 and D65535. Take AH06XA-5A
for example. The original input registers are D0~D7, and the original output registers are D8~D11. You can change the
input device range from D0~D7 to D50~D57, and change the output device range from D8~D11 to D100~D103.
 The default input/output device range: D0~D7, and D8~D11
 The user-defined input/output device range: D50~D57, and D100~D103
3 - 1 3