AH Mo t io n – H ar d war e M a nu a l
Wiring the Differential Input Terminals
The direct-current signals ranging in voltage from 5 V to 24 V can pass through the high-speed input terminals
X0.0+~X0.1+, X0.0-~X0.1-, X0.8+~X0.11+, and X0.8-~X0.11- on AH02HC-5A, and the high-speed input terminals
X0.0+~X0.3+, X0.0-~X0.3-, X0.8+~X0.15+, and X0.8-~X0.15- on AH04HC-5A. The frequency of input signals can be
up to 200 kHz. These high-speed input terminals are connected to a differential (two-wire) line driver.
 Wiring differential input terminals (The wiring below is used for high speed and high noise.)
Transistor Output Circuit
_4
Direct-current power supply
The output terminals of a transistor module are open-collector output terminals. If Y0.8 is a pulse train output
terminal of a transistor module, the output current passing through its output pull-up resistor must be greater
than 0.1 A to ensure that the transistor module operates normally.
A relay or a solenoid valve is used as a DC load. A diode is connected in parallel to absorb the surge voltage
which occurs when the load is OFF.
4 - 4 4
Encoder output
A
A-
B
B-
AH04HC-5A
LED
AH04HC-5A
Y0.8
< 0.5A
C0
Transistor output
Emergency stop
high-speed input
Load