The output terminals of a transistor module are open-collector output terminals. If Y0.0/Y0.1 is a pulse train
output terminal of a transistor module, the output current passing through its output pull-up resistor must be
greater than 0.1 A to ensure that the transistor module operates normally.
A relay or a solenoid valve is used as a DC load. A diode is connected in parallel to absorb the surge voltage
which occurs when the load is OFF.
A bulb (incandescent lamp) is used as a DC load. A thermistor is connected in series to absorb the surge
current which occurs when the load is ON.
_4
4 - 9 4
NP N tra nsi stor ou tpu t (si nki ng )
UP
Relay/Sol enoid valv e
Y0 .0
D
ZP
D: 1 N40 01 di od e
P NP tra nsi stor ou tpu t (so ur cin g)
UP
D
Y0 .0
Relay/Solen oid valve
ZP
D: 1 N40 01 di od e
NPN transistor output (sinking)
PNP transistor output (sourcing)
+
DC p owe r su pp ly
+
DC p owe r su pp ly
DC power supply
DC power supply