Analog Output Parameter Setting Values
The parameter setting values are as follows.
■
Signal Type
Setting Value
0
Unused
1
0 to 10V DC
2
-10 to +10V DC
3
0 to 20mA DC
4
4 to 20mA DC
If the setting value is outside the range, a parameter setting error will occur.
■
Data Format
Setting Value
0
Binary data
1
Optional range
If the setting value is 2 to 65,535, a parameter setting error will occur.
■
Min., Max.
The minimum and maximum values can be set only when Optional range is selected as Data Format. Set the
minimum and maximum values between -32,768 and 32,767.
Mixed Analog I/O Module
●
Allocation of device address for the mixed analog I/O module is shown below.
For details on the parameter setting values for analog inputs, refer to " Analog Input Parameter Setting Values" on
page 2-27. For analog outputs, refer to " Analog Output Parameter Setting Values" on page 2-29.
Channel
No.
CH0
CH1
CH2
CH3
CH4
CH5
R/W is the abbreviation for read/write. When R/W, it can be read and written. When R, it can only be read.
When W, it can only be written.
Parameter
R/W
Analog data
R
Analog status
R
Analog data
R
Analog status
R
Analog data
R
Analog status
R
Analog data
R
Analog status
R
Analog data
R
Analog status
R
Analog data
R
Analog status
R
MICRO/I Hardware Manual
Signal Type
Data Format
FC6A-L06A1
FC6A-L06A4
I/O
Address Number
+0
+1
+2
+3
Input
+4
+5
+6
+7
+8
+9
Output
+10
+11
2 Analog I/O Modules
FC6A-L03CN1
FC6A-L03CN4
I/O
Address Number
+0
+1
Input
+2
+3
+4
Output
+5
―
―
―
―
―
―
―
―
―
―
―
―
2-29
2