Out of range error for Analog Input Value (Status: 5, 6)
When the analog input value reaches or exceeds the following upper limit, the out of maximum range error occurs.
When the analog input valuefalls below the following lower limit, the out of minimum range error occurs.
Signal Type
0 to 10V DC
-10 to +10V DC
0 to 20mA DC
4 to 20mA DC
Type K thermocouple
Type J thermocouple
Type R thermocouple
Type S thermocouple
Type B thermocouple
Type E thermocouple
Type T thermocouple
Type N thermocouple
Type C thermocouple
Pt100
Pt1000
Ni100
Ni1000
NTC Thermistor
PTC Thermistor
PTC Thermistor (threshold)
Ohm meter
Expansion 0 to 20mA DC
Expansion 4 to 20mA DC
*1 Out of minimum range error occurs when a resistance of 200 kΩ or higher is connected.
*2 Out of maximum range error occurs when a resistance of 100 Ω or lower is connected.
Lower Limit Value
-0.2 V
-10.4 V
-0.4 mA
3.68 mA
-200.0°C
-200.0°C
0.0°C
0.0°C
0.0°C
-200.0°C
-200.0°C
-200.0°C
0.0°C
-200.0°C
-200.0°C
-60.0°C
-60.0°C
*1
-90.0°C or 200 kΩ
100 Ω
100 Ω
100 Ω
-0.4 mA
1.20 mA
MICRO/I Hardware Manual
2 Analog I/O Modules
Upper Limit Value
10.2 V
10.4 V
20.4 mA
20.32 mA
1,300.0°C
1,000.0°C
1,760.0°C
1,760.0°C
1,820.0°C
800.0°C
400.0°C
1,300.0°C
2,315.0°C
850.0°C
600.0°C
180.0°C
180.0°C
*2
150.0°C or 100 Ω
10 kΩ
10 kΩ
32 kΩ
23.54 mA
23.17 mA
2
2-21