External Interfaces - IDEC MICRO/I HG2J-7U Hardware Manual

Table of Contents

Advertisement

1.4 External Interfaces

• Make sure to turn off the power to the HG2J-7U before wiring each interface.
• The serial interface (COM) can be used as the RS232C and RS422/485 interfaces at same time.
• Use the SELV (Safety Extra-Low Voltage) circuit to connect each interface.
Serial Interface (COM)
Use applicable cables for wiring and recommended ferrules (made by IDEC, Phoenix Contact or Weidmüller) as
follows.
Interface Specification
Connector
Applicable cable
Conductor Type
*1
Wire Strip Length
Recommended ferrule
No.1
No.
Name
1
SD
2
RD
3
RS
4
CS
5
SG
6
SDA
7
SDB
8
RDA
9
RDB
Only one ferrule can be inserted into a terminal hole.
Please set another terminal block in the vicinity of the main unit and connect SG when using RS232C and
RS422/485 requiring crossover wiring at the same time. And separate the communication cables so that
they do not affect each communication waveform when using RS232C and RS422/485 at the same time.
*1 Strip the sheath of the wire 8 to 9 mm from the end.
8 to 9 mm
RS232C, RS422/485
Detachable Terminal Block 9-pin
AWG16 to 28
Solid wire or Stranded wire
8 to 9 mm
ST3L-H025-12WJ
S3TL-H034-12WT
S3TL-H05-14WA
S3TL-H075-14WW
(IDEC)
No.9
I/O
OUT
Send Data
IN
Receive Data
OUT
Request to Send
IN
Clear to Send
Signal Ground
OUT
Send Data (+)
OUT
Send Data (-)
IN
Receive Data (+)
IN
Receive Data (-)
MICRO/I Hardware Manual
AI 0,25-8YE
AI 0,34-8TQ
AI 0,5-8WH
AI 0,75-8GY
(Phoenix Contact)
Function
1 HG2J-7U
H0,25/12 HBL
H0,34/12 TK
H0,5/14 OR
H0,75/14 W
(Weidmüller)
Communication type
RS232C
RS422/485
1-3