IDEC MICRO/I HG2J-7U Hardware Manual page 127

Table of Contents

Advertisement

Sampling Time
Analog values are converted to digital values at the interval of the sampling time. Depending on the analog I/O
module, you may be able to change the sampling time setting.
Type
FC6A-J2C1
FC6A-J2C4
FC6A-J4A1
FC6A-J4A4
FC6A-J8A1
FC6A-J8A4
FC6A-J4CN1
FC6A-J4CN4
FC6A-J4CH1Y
FC6A-J4CH4Y
FC6A-J8CU1
FC6A-J8CU4
FC6A-L06A1
FC6A-L06A4
FC6A-L03CN1
FC6A-L03CN4
*1 When the Sampling Time is set to 30 milliseconds, the modules may be more easily affected by commercial power supply
noise (50/60 Hz noise) and fluctuations in input values may become larger. If there are large fluctuations in input values,
change the Sampling Time to 120 milliseconds.
Signal Type
0 to 10V DC
-10 to +10V DC
0 to 20mA DC
4 to 20mA DC
0 to 10V DC
-10 to +10V DC
0 to 20mA DC
4 to 20mA DC
0 to 10V DC
-10 to +10V DC
0 to 20mA DC
4 to 20mA DC
Expansion 0 to 20mA DC
Expansion 4 to 20mA DC
0 to 10V DC
-10 to +10V DC
0 to 20mA DC
4 to 20mA DC
Thermocouple
Resistance thermometer
Thermocouple
Thermocouple
NTC Thermistor, PTC Thermistor
PTC Thermistor (threshold)
Ohm meter
0 to 10V DC
-10 to +10V DC
0 to 20mA DC
4 to 20mA DC
0 to 10V DC
-10 to +10V DC
0 to 20mA DC
4 to 20mA DC
Thermocouple
Resistance thermometer
MICRO/I Hardware Manual
2 Analog I/O Modules
Sample Time
1 msec
1 msec
1 msec
1 msec
1 msec or 10 msec
1 msec or 10 msec
1 msec or 10 msec
1 msec or 10 msec
1 msec or 10 msec
1 msec or 10 msec
1 msec or 10 msec
1 msec or 10 msec
1 msec or 10 msec
1 msec or 10 msec
100 msec or 10 msec
100 msec or 10 msec
100 msec or 10 msec
100 msec or 10 msec
104 msec
104 msec
*1
120 msec or 30 msec
104 msec
104 msec
104 msec
104 msec
1 msec or 10 msec
1 msec or 10 msec
1 msec or 10 msec
1 msec or 10 msec
100 msec or 10 msec
100 msec or 10 msec
100 msec or 10 msec
100 msec or 10 msec
104 msec
104 msec
2