IDEC MICRO/I HG2J-7U Hardware Manual page 135

Table of Contents

Advertisement

Analog Input Parameter Setting Values
The parameter setting values are as follows.
Signal Type
Setting Value
0
Unused
1
0 to 10V DC
2
-10 to +10V DC
3
0 to 20mA DC
4
4 to 20mA DC
5
Type K thermocouple
6
Type J thermocouple
7
Type R thermocouple
8
Type S thermocouple
9
Type B thermocouple
10
Type E thermocouple
11
Type T thermocouple
12
Type N thermocouple
13
Type C thermocouple
14
Pt100
15
Pt1000
16
Ni100
17
Ni1000
18
NTC Thermistor
19
PTC Thermistor
20
PTC Thermistor (threshold)
21
Ohm meter
22
Expansion 0 to 20mA DC
23
Expansion 4 to 20mA DC
If the setting value is outside the range, a parameter setting error will occur.
Data Format
Setting Value
0
Binary data, Binary data (12bit)
1
Optional range, Optional range (12bit)
2
Celsius (℃), Resistance (Ω), Binary data (16bit)
3
Fahrenheit (℉), Optional range (16bit)
If the setting value is 4 to 65,535, a parameter setting error will occur.
Min., Max.
The values of Min. and Max. can be set only when Data Format is set to Optional range. Set the minimum and
maximum values between -32,768 and 32,767. However, when Signal Type is set to PTC Thermistor (threshold),
set the values of Min. and Max. between 100 and 10,000.
Signal Type
Data Format
MICRO/I Hardware Manual
2 Analog I/O Modules
2
2-27