2 Analog I/O Modules
Data Format
The analog output value can be handled as the set data format. There are two data formats for the analog outputs.
YES: Supported, NO: Not supported
Data Format
Binary data
Optional range
Min., Max.
The value written to the data register is output from the analog output. The values of Min. and Max. that can be
written are determined by the set Signal Type and Data Format. A parameter setting error occurs when a value is
set that exceeds the value of Min. or Max. .
The minimum and maximum values that correspond to the signal types and data formats are as follows.
Signal Type
0 to 10V DC
-10 to +10V DC
0 to 20mA DC
4 to 20mA DC
Data
The analog output data for the analog output set with the Signal Type, the Data Format, the Min. and the Max. is
stored in the data registers in the END progressing of each scan. The actual analog output data is not guaranteed
when the analog output Status is a value other than "0". However, 0V is output when Signal Type is set to -10 to
+10V DC.
Status
The status of the analog output Data is stored in data registers.
Status
0
1
2
3
4
5 to 65,535
*1 Min. and Max. can be set only when Data Format is set to Optional range. Set the values of Min. and Max. between -
32,768 and 32,767.
2-24
FC6A-K2A1
FC6A-K2A4
YES
YES
Binary data
0 to 4,095
-2,048 to 2,047
0 to 4,095
0 to 4,095
Operating normally
Reserved
Initializing
Parameter setting error
Hardware fault (external power supply error)
Reserved
MICRO/I Hardware Manual
FC6A-K4A1
FC6A-L06A1
FC6A-K4A4
FC6A-L06A4
YES
YES
Data Format
-32,768 to 32,767
-32,768 to 32,767
-32,768 to 32,767
-32,768 to 32,767
Description
FC6A-L03CN1
FC6A-L03CN4
YES
YES
YES
YES
*1
Optional range