Commissioning
Parameter
Assign frequency output
Minimum frequency value
Maximum frequency value
104
Prerequisite
The Frequency option is
selected in the Operating
mode parameter (→ 101).
The Frequency option is
selected in the Operating
mode parameter (→ 101)
and a process variable is
selected in the Assign
frequency output parameter
(→ 104).
The Frequency option is
selected in the Operating
mode parameter (→ 101)
and a process variable is
selected in the Assign
frequency output parameter
(→ 104).
Description
Select process variable for
frequency output.
Enter minimum frequency.
Enter maximum frequency.
Proline Promass H 300 PROFINET
Selection / User
Factory setting
interface / User
entry
• Off
Off
• Mass flow
• Volume flow
• Corrected volume
flow
*
• Target mass flow
*
• Carrier mass flow
• Target volume
*
flow
• Carrier volume
*
flow
• Target corrected
*
volume flow
• Carrier corrected
*
volume flow
• Density
• Reference density
*
• Concentration
• Temperature
• Carrier pipe
*
temperature
• Electronic
temperature
• Oscillation
frequency 0
• Oscillation
*
amplitude 0
• Frequency
*
fluctuation 0
• Oscillation
*
damping 0
• Oscillation
damping
*
fluctuation 0
*
• Signal asymmetry
*
• Exciter current 0
*
• HBSI
• Pressure
• Application
*
specific output 0
• Application
*
specific output 1
• Index
inhomogeneous
medium
• Index suspended
*
bubbles
0.0 to 10 000.0 Hz
0.0 Hz
0.0 to 10 000.0 Hz
10 000.0 Hz
Endress+Hauser
Need help?
Do you have a question about the Proline Promass H 300 PROFINET and is the answer not in the manual?