Commissioning; Function Check; Switching On The Measuring Device; Connecting Via Fieldcare - Endress+Hauser Proline Promass H 300 PROFINET Operating Instructions Manual

Coriolis flowmeter
Table of Contents

Advertisement

Proline Promass H 300 PROFINET
Endress+Hauser
10

Commissioning

10.1

Function check

Before commissioning the measuring device:
Make sure that the post-installation and post-connection checks have been performed.
• "Post-installation check" checklist→  28
• "Post-connection check" checklist →  46
10.2

Switching on the measuring device

After a successful function check, switch on the measuring device.
 After a successful startup, the local display switches automatically from the startup
display to the operational display.
If nothing appears on the local display or a diagnostic message is displayed, refer to
the section on "Diagnostics and troubleshooting" →  146.
10.3

Connecting via FieldCare

• For FieldCare →  68 connection
• For connecting via FieldCare →  70
• For the FieldCare →  71 user interface
10.4

Setting the operating language

Factory setting: English or ordered local language
X X X X X X X
X
XX
Main menu
1.
2.
3.
4.
 26
Taking the example of the local display
X
20.50
XX
0104-1
Display language
English
Operation
Setup
Display language
English
Ã
Deutsch
Español
Français
Display language
Ã
English
Deutsch
Español
Français
Commissioning
0104-1
0104-1
Hauptmenü
0104-1
Sprache
Deutsch
Betrieb
Setup
A0029420
87