Route Group Categories - Bosch D9412GV4 Program Entry Manual

Table of Contents

Advertisement

D9412GV4/D7412GV4/D7212GV4
Keypad Programming of the R# Backup Device
D1255
1.
2.
3.
4.
5.
When the keypad reads Parameter Saved, your selection has been configured.
D1260
1.
2.
3.
4.
5.
When the keypad reads Parameter Saved, your selection has been configured.
3.3.10

Route Group Categories

Fire Reports
NOTICE!
To meet UL 864 requirements for Central Station and Remote Station applications (D9412GV4
and D7412GV4), enable Fire Reports.
Selecting Yes enables a report to be sent when the event occurs.
Report
R# Fire Alarm
R# Fire Restore (Alarm)
R# Fire Missing
R# Fire Trouble
R# Fire Supervision
R# Fire Restore (T/M/S)
R# Fire Cancel
R# Fire Sup Miss
Table 3.6 Fire Reports
Bosch Security Systems, Inc.
Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the ROUTE GRP 1 - 4 option.
At the ROUTE GRP 1 - 4 prompt, enter the route group number you wish to configure and
press [ENT]. The keypad reads RT GRP 1 PRIMARY, and then the current configuration
(for example, SDI 88 PATH 4).
Press [NEXT] to advance to the RT GRP 1 BACKUP option. The Primary device cannot be
set to No Device before setting the Backup Destination.
To change the configuration, press [ENT] when the current configuration shows, and
then press [NEXT] or [PREV] to scroll through the options, as listed in Section R# Backup
Device, page 32.
When the keypad reads the desired configuration option, press [ENT] to select it.
Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the Route Group 1 - 4 option.
At the Route Group 1 - 4 prompt, enter the route group number you wish to configure
and press [ENTER]. The keypad reads Rt Group 1 Primary, and then the current
configuration (for example, SDI 88 PATH 4).
Press the Backup softkey. The keypad reads Rt Group 1 Primary, and then the current
configuration (for example, SDI 88 PATH 4). The Primary device cannot be set to No
Device before setting the Backup Destination.
To change the configuration, press the Edit softkey, and then press the Next or the
Previous softkey to scroll through the options, as listed in Section R# Backup Device,
page 32.
When the keypad reads the desired configuration option, press the Save softkey to select
it.
Program Entry Guide
Selection
Report Description
Yes, No
Fire Event
Yes, No
Fire restoral from alarm
Yes, No
Missing Fire point
Yes, No
Fire trouble
Yes, No
Fire supervisory
Yes, No
Fire restoral from trouble, missing, or bypass
Yes, No
Canceled fire alarm
Yes, No
Fire supervisory missing
Panel and Area Wide Parameters | en
F.01U.218.312 | 04 | 2012.03
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412gv4D7212gv4

Table of Contents