168 en | Schedules (Skeds)
11
Execute Custom Func: This function emulates
any of the custom functions assigned to the
keypad that can be executed by a user from
the keypad. When a sked executes a custom
function, it is subject to the scope of the
selected keypad. Cmd Center and Custom
Func prompts appear after entering Function
Code 11. Both entries are required.
12
Contact RPS: This function attempts to
contact an Unattended RPS at the configured
time. The control panel's account in RPS
controls the operations performed upon
successful contact.
CAUTION!
Avoid having multiple functions occur at the same time at the same address. Functions can
clash and the effect on the control panel is unpredictable.
NOTICE!
Ensure that the Custom Function being executed or any of the commands nested inside the
Custom Function are not passcode protected.
NOTICE!
Do not program multiple skeds to execute at the same keypad during the same time.
Do not program skeds to execute at times when a user is likely to be executing functions at
the keypad. If it is necessary to do so, there are two ways to work around the situation:
Default:
Selection:
13
Adjust Time Forward One Hour:This sked function is used to make adjustments to the control panel's clock. A
typical application is to program this to go into effect at 2:00 AM on the date that Daylight Saving Time begins
(during the springtime). No Time Change Report is sent or logged, but the new time appears in the next report
logged.
No other parameters require input for this option.
F.01U.218.312 | 04 | 2012.03
For a D1255 keypad type, program "C","C"at the beginning of the Custom Function Key
Strokes entry. This aborts the user's function and allows the sked to execute.
Program the sked to execute at an address (Command Center) with no keypad physically
attached to it. The CC # must be assigned to an area and have the appropriate scope
programmed.
0
0 to 24, 28, 29
Program Entry Guide
S## Cmd Center
Default: Blank (0)
Selections: Blank (0), 1 to
8
Identify the specific keypad
(CC #) where the Custom
Function is entered. Only
one keypad can be assigned
for this sked function.
S## Custom Func
Default: Blank (0)
Selections: Blank (0), 128
to 143 for D9412GV4, 128
to 131 for D7412GV4 and
D7212GV4
Enter the custom function
this sked executes.
D9412GV4/D7412GV4/D7212GV4
Blank (0)
No keypad is
specified for
Custom Function
activation.
1 to 8
Command center
(keypad) address
specified for
Custom Function
activation.
Blank (0)
128 to 143
No Custom
Function is
activated.
Custom Function
to activate.
Bosch Security Systems, Inc.