When the Fire and Burg Bells share the same output and a Fire Bell occurs while the Burg Bell
is ringing, the Fire Bell pattern overrides the Burg Bell pattern. At the end of the fire time, the
burg pattern resumes.
When the Fire and Burg Bells share the same output and a Burg Bell occurs while a Fire Bell
sounds, the control panel waits until the Fire time expires before starting the Burg Bell.
Either a single bell (panel-wide) or a number of bells (area-wide) can be used on the control
panel. For programming these applications, refer to Section 3.14.1 Area Relays, page 118.
When both Fire and Burg Bells occur simultaneously and a user enters a valid passcode, a Fire
Cancel Report for the fire alarm and a Cancel Report for the burg alarm is sent to the central
station if Cancel Reports is programmed Yes.
A# Fire Time
Default:
Selection:
Enter the number of minutes the bell rings for Fire Alarm points. The relay activated for this
time is programmed in A# Fire Bell in Area Relays.
The bell output begins as soon as the fire alarm occurs. It shuts off the bell when the
programmed number of minutes expires.
If programmed for 1 min, the output can be anywhere from 0 to 60 sec of bell time. Program
Fire Time for 2 min or more to ensure you have ample output time.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), program A# Fire Time for at least
5 min. Check with your AHJ to determine the appropriate bell time for your geographical area.
A# Fire Pattern
Default:
Selection:
Steady
Pulse
CA Standard
TempCode3
Select the bell pattern this area uses to signal an alarm on a Fire point.
NOTICE!
When an alarm occurs on two Fire points sharing the same relay, the bell pattern of the most
recent fire event takes precedence.
A# Burg Time
Default:
Selection:
Bosch Security Systems, Inc.
6 min
1 min to 90 min
Pulse
Steady, Pulse, CA Standard, TempCode3
Steady Output
Pulse March Time
120 beats per minute, at an even tempo
California Standard
10 sec On + 5 sec Off + 10 sec On + 5 sec Off. This sequence repeats
until bell time expires.
Temporal Code 3
0.5 sec On, 0.5 sec Off, 0.5 sec On, 0.5 sec Off, 0.5 sec On, 1.5 sec Off;
pattern repeats. This sequence repeats for a minimum of 3 min and
with a ± 10% tolerance.
6 min
1 min to 90 min (in one-minute increments)
Program Entry Guide
Panel and Area Wide Parameters | en
F.01U.218.312 | 04 | 2012.03