Bosch D9412GV4 Program Entry Manual page 51

Table of Contents

Advertisement

D9412GV4/D7412GV4/D7212GV4
Program the length of time the AC power must be off before the message SERVC AC FAIL
shows on the keypads. The response to restoral of AC power is delayed for the same amount
of time. This prompt applies to AC failure events generated by the control panel, any installed
SDI2 bus power supply modules and any installed RF Repeaters.
AC Fail/Restoral Report
Default:
Selection:
Yes
No
AC Power Supervision Reports are sent to the central station and local printer at the time
programmed for AC Fail Time. This prompt applies to AC failure events generated by the
control panel, any installed SDI2 bus power supply modules, and any installed RF repeaters.
AC Tag Along
Default:
Selection:
Yes
No
Send AC Reports only if any other event occurs while AC is off-normal.
NOTICE!
If AC Tag Along is set to Yes and a subsequent event is generated, the AC Fail Event is sent
first, before sending any subsequent events.
NOTICE!
AC Tag Along is required for NFPA and UL 864 Commercial Fire systems (D9412GV4 and
D7412GV4). Be sure to program AC Fail/Restoral Report as No if AC Tag Along is
programmed Yes.
AC/Battery Buzz
Default:
Selection:
Yes
No
Initiates a panel-wide trouble tone at keypads when AC fails or battery is low or missing. This
program item does not prevent the SERVC AC FAIL or SERVC BATT LOW displays.
NOTICE!
To comply with NFPA standards and UL 864 requirements for Commercial Fire systems
(D9412GV4 and D7412GV4), program this item as Yes.
NOTICE!
If annunciating panel-wide troubles at a keypad with CC# Scope set to Panel Wide is
undesirable, set CC# Trouble Tone to No. Refer to Section Command Center, page 79 for
keypad configurations.
Battery Fail/Restoral Report
Default:
Selection:
Bosch Security Systems, Inc.
No
Yes or No
Send AC Fail and AC Restoral Reports.
Do not send AC Fail and AC Restoral Reports.
Yes
Yes or No
Send AC messages as tag along events.
Do not send AC messages as tag along events.
No
Yes or No
Initiates panel-wide trouble tone at all keypads.
Does not initiate panel-wide trouble tone at keypads.
Yes
Yes or No
Program Entry Guide
Panel and Area Wide Parameters | en
F.01U.218.312 | 04 | 2012.03
51

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412gv4D7212gv4

Table of Contents