D9412GV4/D7412GV4/D7212GV4
NOTICE!
Avoid programming the Open Early Begin time before a time that is between another
window's Open Window Start and Open Window Stop times.
Disabled windows have a beginning time of 00:00. If the entry for this prompt is 00:00, but
times are programmed for Close Window Start and Close Window Stop, the window is
disabled.
To disable the window, both the hours and minutes spaces must be 00:00.
00:00 is midnight, 23:59 is 11:59 PM. Make entries using a 24-hour clock (for example, 7:00
AM is entered as 07:00, 2:45 PM is entered as 14:45).
If the window must activate on the same day as it is programmed, reboot the control panel to
activate the window immediately.
W# Close Window Start
Default:
Selection:
Enter the time that you want the control panel to start the Closing Window. The window goes
into effect at the beginning of the minute.
00:00 is midnight, 23:59 is 11:59 PM. Make entries using a 24-hour clock (for example, 7:00
AM is entered as 07:00, 2:45 PM is entered as 14:45).
This program item is one of three required to create a Closing Window. To program a Closing
Window, Close Early Begin and Close Window Stop must also be programmed.
If the area is not armed when the Close Window Start time comes, a warning tone sounds and
PLEASE CLOSE NOW appears at the keypad. To temporarily silence the tone, press the [ESC]
key on the keypad. The warning tone restarts in 10 min if the area is not armed.
Refer to Section W# Close Early Begin, page 158 in this section for explanations of report
features.
W# Close Window Stop
Default:
Selection:
Enter the time that you want the control panel to end the Closing Window. The window stops
at the end of the minute.
00:00 is midnight, 23:59 is 11:59 PM. Make entries using a 24-hour clock (for example, 7:00
AM is entered as 07:00, 2:45 PM is entered as 14:45).
This program item is one of three required to create a Closing Window. To program a Closing
Window, Close Early Begin and Close Window Start must also be programmed.
If the area is not armed by the time the Close Window Stop time expires, the control panel
generates a Fail to Close Report if enabled in Fail To Close.
Closing Reports generated between the Close Window Start time and Close Window Stop
time can be suppressed by programming Disable O/C in Window as Yes. Refer to Section W#
Close Early Begin, page 158 for other explanations of report features.
Do not use a time of 23:59 as a window stop time unless the window continues on the next
day at 00:00. Fail to Close Reports are not sent, and the Auto Close feature does not work for
windows that stop at 23:59.
Do not program a single window to cross the midnight boundary. The window stop time must
be later than the window start time. To program a window that effectively crosses the
midnight boundary, you must program two windows.
For example, to program windows for an area that closes between 11:30 PM and 12:30 AM,
five days a week, use two windows as shown in Figure 6.5, Page 161.
Bosch Security Systems, Inc.
00:00
HH:MM (hours and minutes)
00:00
HH:MM (hours and minutes)
Program Entry Guide
Schedules (Skeds) | en 159
F.01U.218.312 | 04 | 2012.03

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412gv4D7212gv4

Table of Contents