Page 1
D9412G/D7412G Program Entry Guide Control Panels...
Page 2
D9412G/D7412G | Program Entry Guide | EN | 2 Application Note: Trademarks These are notes and clarifications of ® CoBox is a registered trademark of Lantronix different aspects of the application. ® Windows is either a registered trademark of Microsoft...
D9412G/D7412G | Program Entry Guide | Table of Contents EN | 3 2.10.1 Cmd Cntr (Command Center) Assignment.. 46 Table of Contents 2.10.2 Area Text ............50 2.10.3 Custom Function..........51 Introduction............5 2.11 User Interface ........... 53 How to use this Program Entry Guide.....5 2.11.1 Commands............
Page 4
D9412G/D7412G | Program Entry Guide | Table of Contents EN | 4 Miscellaneous..........127 Table 21: Programming Four Digit Account Numbers ............35 Cross Point Parameters ........128 Table 22: Programming Ten Digit Account RADXAXS .............131 Numbers ............35 Door Profile.............131 Table 23: Verify Time........... 37 Strike Profile............133...
D9412G/D7412G | Program Entry Guide | 1.0 Introduction EN | 5 Differences Between the D9412G 1.0 Introduction and D7412G Table 2 describes the differences between the D9412G How to use this Program Entry Guide and the D7412G Control Panels. This guide addresses the programming of the...
D9412G/D7412G | Program Entry Guide | 1.0 Introduction EN | 6 New Features The items shown Table 3 are new features added to the D9412G/D7412G Control Panels since version 6.10. Table 3: New Features Feature Description Ground Fault Detect For the D9412G/D7412G to detect ground fault conditions, the earth ground terminal on the (Version 6.10)
Page 7
Interface, which connects directly to ZONEX 1 and ZONEX 2 (D9412G only) and an Inovonics (Version 6.30) FA400 Wireless Receiver, up to 238 wireless transmitters can be added to a D9412G (up to 67 can be added to the D7412G). Each D8125INV supports up to 119 wireless transmitters (or 67 if connected to a D7412G).
D9412G/D7412G | Program Entry Guide | 1.0 Introduction EN | 8 Product Handlers Programming the 9000 Series requires multiple product handlers. The availability of each handler is indicated in Table 4. See the control panel specific Release Notes to determine the most up-to-date handler versions.
D9412G/D7412G | Program Entry Guide | 1.0 Introduction EN | 9 Programming the Control Panel with the D5200 Programmer Latch the jumper in the upper right hand corner of the control panel labeled as RESET on the PCB and Reset Pin on the faceplate.
Page 10
D9412G/D7412G | Program Entry Guide | 1.0 Introduction EN | 10 Notes: Bosch Security Systems | 10/03 | 47775E...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 11 The control panel is pre-programmed with a 7-second dial tone detect period. When a dial tone is 2.0 9000MAIN detected or the waiting period ends, the control Use this programming module to define the panel begins to dial.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 12 Phone Parameters Point/User Flag The program items in this category describe panel- Default: wide characteristics for telephone dialing, receiver format, and supervision. Selection: Yes or No Modem Format The control panel sends a flag with...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 13 D6000: Opening/Closing User ID numbers are Table 6: Modem IIIa Communication Format identified at the receiver as ZONEs (same identification as independent points). Data - User ID Numbers Table 8: Zones...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 14 Phone Supv Time Buzz on Fail Default: Blank Default: Selection: Selection: Blank or 10 to 240 Yes or No Blank No phone line supervision. Generate panel-wide trouble tones and...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 15 Press the [SPACE] bar to scroll through the BFSK Duress Code selections. Press [ENTER] when the correct selection appears in the display. Default: Use this program item only when the control...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 16 2.3.3 Programming a Primary and Backup 2.3.6 Routing Destination Communication Destination Failures R# Primary Device R# Primary Device Each route number has an When the fails to connect with R# Backup Device .
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 17 Route # R# Backup Device Default: Default: Blank Selection: Selection: 1 to 4 Blank, 1 to 4 First group sent Phone 1 or SDI Path 1 is this group’s...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 18 Fire Reports Burglar Reports Selecting Yes enables a report to be sent when the Selecting Yes enables sending a report when the event occurs. event occurs. Table 9: Diagnostic Reports...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 19 Restoral Reports are not sent if the User Reports control panel is reset after a point is Selecting Yes enables a report to be sent when the bypassed and then the point is event occurs.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 20 Test Reports Table 12: Test Reports 0101 To send a single Test Report (R# Test 0101 Report), enable Sked Function Code #9 Report Selections Description 0101 (Test Report) in the Skeds section of the...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 22 RAM Reports Point Reports Selecting Yes enables sending a report when the Selecting Yes enables a report to be sent when the RAM Passcode Event occurs. event occurs. RAM Access Fail can indicate a...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 23 User Chng Reports Table 19: Access Reports Selecting Yes enables a report to be sent when the event occurs. Report Selections Description Table 18: User Change Reports R# Access...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 24 2.4.2 Programming a Duplicate Report If you use a D9133TTL-E as a Primary To allow an event within a group to report to Device in any of the route groups, follow...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 25 Programming the Pager Phone Number RG# Primary Pager To program the pager phone number, enter the Default: number used to reach the pager, followed by pauses. Entering C creates a 3-second pause (example:...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 26 For example, the phone number 2773074***CC (7 digit pager phone number followed by three Table 20: continued asterisks and two pauses) produces the following pager display: [1234-001-011] (three fields display at...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 27 Power Supervision Table 20: continued AC Fail Time Event Event Default: Event Description Priority Number Parameters Changed Selection: 1 to 90 (Blank and 0 are invalid) RAM Access OK...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 28 An additional AC Fail Event is transmitted after Firmware versions 6.10 and lower: To 6 hours if the AC Fail condition is still present. eliminate AC Reporting, AC Tag Along •...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 29 Printer Parameters AC/Battery Buzz Up to three D9131A Parallel Printer Interface Default: Modules can be connected to the D9412G’s (one printer for the D7412G’s) SDI bus. Each printer is...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 30 See the report tables in Section 2.3 When P## Supervised is set to Yes and Routing to identify the events that print. all Printer Event Groups (such as P##...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 31 When RAM programming changes parameters, a P## Auto Functions Event Parameters Changed Report is sent to the D6500/D6600. If any programming changes are Default: Program Record Sheet made, perform a Reset-bye.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 32 RAM Passcode RAM Call Back Default: 999999 Default: Selection: Selection: 0 to 9, A to F Yes or No (six characters required) When the control panel hears the Enter six characters. Do not use a space in the proper RAM passcode, it hangs up the passcode.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 33 Ram Ph 0101 Program this item No if it causes false 0101 seizures of the phone line or if you are not 0101 Default: Blank using RAM (this indicates a device using...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 34 A Cancel and Fire Cancel Report is created when a Miscellaneous passcode is entered to silence an Alarm Bell or a Fire Bell before the bell time expires. Duress Type...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 36 Figure 2: Account Number Entry A# Delay Res Default: Selection: Yes or No Point Restoral Report is not sent until the bell time expires or user 1 - RPS account number entry acknowledges alarm condition.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 37 Points are programmed individually to activate the A# Auto Watch verification feature. See Section 4.1 Point Index. Any resettable Fire point can activate alarm verification Default: for the area to which it is assigned. Use separate area...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 38 A# Duress Enable Default: Selection: Yes or No Enable Duress alarm for this area. Disable Duress alarm for this area. This entry determines if this area allows duress Duress Type alarms to be generated.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 39 A# Area Type Default: Regular Selection: Regular, Master, Associate, or Shared Regular Arms or disarms as an independent area. Master Does not allow arming for this area unless all associate areas with the same A# account number are master exit delay arming or master armed.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 40 Access Control Readers Assigned to the Shared 2.9.3 Shared-Area Characteristics Area Arming a Shared Area The shared area momentarily disarms then begins Requires all associate areas to be armed. As soon as...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 41 A# Fire Time A# Burg Time Default: Default: Selection: 1 minute to 90 minutes Selection: 1 minute to 90 minutes (in 1 minute Enter the number of minutes the bell rings for Fire increments) Alarm points.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 42 2.9.5 Open/Close Options Programming determines if Opening, All Normal If a 24-hour point alarms while the area is Closing, and Force Arm/Bypass Closing Events are disarmed, arming that area with a reported to the remote central station.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 43 Combination Account and Area Opening and A# Acct O/C Closing Reports Default: To send both account openings and closings, and individual area openings and closings for all areas in...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 44 Determines if opening and closing activity is A# Area O/C reported when it occurs inside an Opening or Closing Window as programmed in O/C Windows. Default: Reports are always logged and printed on a local...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 45 A# Fail to Close A# Restrictd O/C Default: Default: Selection: Selection: Yes or No Yes or No Fail to Close Report occurs for this area if the Restrict Opening and Closing Reports for this...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 46 2.10 Command Center A# Perimeter O/C This programming module contains three Default: programming categories: Cmd Cntr Assignment, Area Text, and Custom Function. Selection: Yes or No 2.10.1 Cmd Cntr (Command Center) Assignment...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 47 CC# Supervised CC# Scope Default: Program Record Sheet Default: Program Record Sheet Selection: Selection: Yes or No Panel Wide, Custom, No Keypad, Area, and Account Only one command center can be installed for this CC SDI address.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 48 CC# A1[through A8] in Scope CC# Entr Cycl Dr Default: See preceding important note Default: Selection: Yes or No Selection: Yes or No Include this area in the scope of this The [ENTER] key is used to cycle the command center.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 49 Determines whether this command center, or any CC# Assign Door command center with the same address setting, emits the panel-wide trouble tones (power, phone, Default: Blank SDI bus, and Zonex bus).
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 50 When a D1260 Alpha V Command Center is 0101 This prompt allows you to manage the 0101 installed at this command center address, this item tone by command center. Exit Tone can 0101 must be set to Yes.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 51 2.10.3 Custom Function Area # Acct Is On Custom functions are a way to simplify use of Program Record Sheet Default: complex keystroke sequences entered at the command center. These items are similar to speed...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 52 CF### Key Strokes Table 24: CF### Custom Function Keystrokes Default: Program Record Sheet Command Keystroke Selection: Up to 32 characters: 0 to 9, A, B, C, 1 (Master arm area)
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 53 The D9412G/D7412G Program Record Sheet lists the • Custom Functions can perform several tasks at commands available with the system. Command once. For example: numbers are shown in the column labeled To toggle relays 7, 8, and 9 in one Custom Command.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 54 Master Arm Delay Perim Delay Default: Default: Selection: Selection: Blank, E, or P Blank, E, or P #5 Perimeter Delay Arm [COMMAND][3] Passcode: Required for all users with Master Arm Delay enabled for their Delay arms all Perimeter points in the area where authority level.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 55 View Area Stat Fire Test Default: Default: Selection: Selection: Blank, E, or P Blank, E, or P #8 View Area Status (MENU FUNCTION only) #12 Fire Test [COMMAND][5][8] Use this function to view the armed status of all...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 56 Access Ctl Level Add User Default: Default: Selection: Selection: Blank, E, or P Blank, E, or P #37 Access Control Levels (MENU FUNCTION #18 Add User [COMMAND][5][6] only) Use this function to add/change passcodes,...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 57 Print Log Unbypass a Pt Default: Default: Selection: Selection: Blank, E, or P Blank, E, or P #22 Print Event Log (MENU FUNCTION only) #26 Unbypass a Point [COMMAND][0][0]...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 58 Move to Area Default Text Default: Default: Selection: Selection: Blank, E, or P Blank, E, or P #30 Move to Area [COMMAND][5][0] #34 Default Text [COMMAND][5][7] Use this function to temporarily switch the It may be difficult to determine the armed state of an command center’s assignment to a different area.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 59 2.11.3 Authority Level Selections 0101 There are many options available for 0101 Use Section 2.11.3 Authority Level Selections to arming and disarming. This depends on A# 0101 determine which Authority Level can access Area Type and CC# Scope.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 60 L## View Memory L## Perim Instant Program Record Sheet Default: Program Record Sheet Default: Selection: Blank or E Selection: Blank or E #9 View Event Memory [COMMAND][4][0] #4 Perimeter Instant Arm [COMMAND][2]...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 61 Access Control Functions To Walk Test a Door point connected to a D9210B Access Interface Module, the The following functions enable the user to control door must be opened without activating the doors using the command center.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 62 L## Unlock Door Table 27: L## Secure Door-Door Mode Definitions Default: Program Record Sheet Selection: Blank or E Door State Definition Unlock Door (MENU FUNCTION only) Lock Door Normal Door: When a door is in the...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 63 L## Chg Display 0101 Although an individual user (001 through 0101 249) can be deleted separately, take 0101 Program Record Sheet Default: caution. User passcode, token/cards Selection: Blank or E...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 64 L## Move to Area L## User Cmd 9 Program Record Sheet Default: Program Record Sheet Default: Selection: Blank or E Selection: Blank or E #30 Move to Area [COMMAND][5][0]...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 65 D1255 command center displays a Report Levels sequential count after each point is activated L## Force Arm and restored as well as the text for the point. The D1255 command center displays ALL...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 66 L## Passcode Disarm L## Disarm Level Program Record Sheet Program Record Sheet Default: Default: Selection: Blank or E Selection: I, D, or Blank Disarm an area by entering a passcode and pressing Users change the Master Armed state [ENTER].
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 67 2.12 Function List M## CC Address 1 [through 8] The Function List is accessed when the user presses Program Record Sheet Default: [MENU] (or the key corresponding to menu) on the...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 68 • Relay Reports: When relay activity is reported 0101 Check relay status after reprogramming to the receiver (see Section 2.3 Routing), on-board 0101 or resetting the control panel. All relays...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 69 A# Fire Bell 0101 When sharing one relay to reset sensors in 0101 two or more areas, you must program the Default: 0101 following. Failure to do so causes...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 70 A# Area Armed 0101 Burg Time needs a bell period 0101 programmed and A# Duress Enable must 0101 Default: Blank be Yes. This relay activates steadily Selection: Blank, 1 to 128 (1 to 64 for D7412G),...
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 71 2.13.2 Panel-Wide Relays 0101 Programming Tip #4: 0101 The following eleven relay options activate when 0101 Fire Trouble Resound was added to they occur anywhere in the control panel. They are firmware versions 6.20 and later.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 72 Summary Fire Tbl Comm Fail Default: Blank Default: Blank Selection: Blank, 1 to 128 (1 to 64 for D7412G), Selection: Blank, 1 to 128 (1 to 64 for D7412G),...
It is recommended that you use For the D9412G, there are 249 groups (99 groups for the ADD/CHG USER? function to change a the D7412G) consisting of one user with a passcode...
D9412G/D7412G | Program Entry Guide | 3.0 RADXUSR1/RADXUSR2 EN | 74 Figure 3: User Group 122 Example Master User: ID 122. ♦ CRD ID 122-0 ♦ Sub User -1: ID 122-1 CRD ID 122-1 ♦ Sub User -2: ID 122-2.
D9412G/D7412G | Program Entry Guide | 3.0 RADXUSR1/RADXUSR2 EN | 75 A silence bell authority is built into all U### Name authority levels, even if they are the default and none of the available programmable Program Record Sheet Default: functions are enabled. A user passcode...
D9412G/D7412G | Program Entry Guide | 3.0 RADXUSR1/RADXUSR2 EN | 76 U### SU1 through SU3 C/D 0101 Converting hexadecimal to decimal: If 0101 your card label contains letters as well as 0101 Default: Blank numbers, the number is hexadecimal.* Selection:...
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 77 The NEW RECORD program contains default 4.0 RADXPNTS entries and descriptions that match RPS defaults for point indexes. See the D9412G/D7412G Program Point Index Record Sheet for defaults. Use this programming module to construct Point Index personality types for points used in the system.
Page 78
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 78 P ## Description Type Selection Interior: Interior points are armed only by master arming the area. They are NOT armed when using Perimeter Arming functions. These points are typically used to monitor interior detection devices such as interior doors, motion detectors, photoelectric beams, and carpet mats.
Page 79
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 79 P ## Description Type Keyswitch Maintained: Program Point Response as 1. Do not connect initiating devices to a Keyswitch point. Normal: The area is disarmed. Short: When this point changes from normal to open, the area arms.
Page 80
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 80 P ## Description Type Selection D279 (O/C Non-Priority): The D279 provides point arming and disarming independent of the area Point Response arm state. A non-priority D279 point arm state does not affect the area arm state.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 81 4.1.1 Point Responses Applications for Point Responses 9, D, Characteristics of a Fire Point: and E: Reporting: When a group of events occur, the control panel routes and prints out Fire...
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 82 P## Pt Response Program Record Sheet Default: Selection: 0 to F Controlled (Non-24-Hour Points) Point Response Armed Open Armed Short Disarmed Open Disarmed Short 24-Hour Points Point Response Open...
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 83 P## Entry Delay 0101 Entry Tone can also be turned off when 0101 programming your CC Entry Tone, in 0101 Program Record Sheet Default: Section 2.10 Command Center, which...
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 84 If the point restores and the fire alarm is To prevent the command center alarm tone not silenced from the command center, and the A# Burg Alarm bell from sounding,...
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 85 P## Buzz On Fault Default: Blank Selection: Blank, 1 to 3 Selection Operation for Controlled Points Operation for 24-hour Points (Point Types 1, 2, and 3) (Point Type 0)
), to report Alarms, Troubles, and Use this option to cause a relay (1 to 127 for D9412G; 1 to 64 for D7412G) to respond when a Restoral Reports only when the area is armed. This corresponding point with the same number (1 to prompt does not affect local annunciation.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 87 Restoral Reports are still transmitted if the alarm, P## FA Retrnable trouble, or bypass (by Sked, RAM, or Swinger bypass) condition occurred when the area disarmed, and the Default: point restored.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 88 P## Bypassable P## Swinger Byps Default: Default: Selection: Yes or No Selection: Yes or No This point can be bypassed and force Enable Swinger Bypass for this point. armed.
Report. and D7412G to support the Cross Point function. 0101 Bypass Reports do not occur when arming There are 31 Cross Point Groups in the D9412G 0101 the area if the Closing Report is 0101 and ten in the D7412G. Each Cross Point Group...
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 90 P## Fire Point Characteristics of a Fire Point Reporting: When a group of events Default: occur, the control panel routes and prints Selection: Yes or No out Fire Reports first.
These entries assign point indexes to Points 1 to 127, Use this option only with Fire points to designate 129 to 247 for the D9412G and Points 1 to 75 for the them for alarm verification. D7412G, and assigns the points to the areas. Also...
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 92 P### Point Index P### Debounce Program Record Sheet Default: Default: Selection: Blank (00) to 31 Selection: 1 to 15 P## Index This entry selects one of the 31 codes .300 seconds...
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 93 P### BFSK/Relay Two relays can activate when this point goes into alarm if the P## Rly Resp Type Program Record Sheet Default: for this point is programmed. Selection: 0 to 9...
This entry selects one of the digits shown for reporting in BFSK or for activating relays 73 to 80 CMD7 BFSK/Relay (on the D9412G) or relays 9 to 16 (for the D7412G) P### when a COMMAND 9 is initiated (see the...
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 95 5.0 RADXSKED Table 31: Window Selections Windows Use this programming module to define the Selection Sked # Window Sked # Windo windows for Opening and Closing and User Access.
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 96 Start and Open Window Stop time creates a W# Monday local event in the Panel log but does not send the Opening Report to the central station. Default: Disarming the area after the Open Window Stop...
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 97 If the area is not disarmed by the time the Open W# Open Window Stop Window Stop time expires, the control panel generates a Fail to Open Report if enabled in Fail...
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 98 Table 32: Programming for Two Same Day Opening Windows (see Figure 4) Open Close eXcept Early Early Holiday Begin Start Stop Begin Start Stop Day of Week Holiday Index...
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 99 Disable/Restart the control panel to activate Enter the time that you want the control panel to today’s window. If you are programming a end the Closing Window. The window stops at the window that needs to activate on the same day end of the minute.
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 100 W# Xept Holiday W# Holiday 2 Default: Default: Selection: Yes or No Selection: Yes or No Do not activate this window on W# Holiday 3 holidays. Default: To use this selection, the window must...
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 101 Table 35: Opening/Closing Windows Worksheet Open Close eXcept Early Early Holiday Begin Start Stop Begin Start Stop Day of Week Holiday Index Area(s) S M T W T F S...
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 102 Table 38: Delivery Schedule* Open Close eXcept Early Early Holiday Begin Start Stop Begin Start Stop Day of Week Holiday Index Area(s) 02 : 30 02 : 45 03 : 00...
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 103 UW# Sunday UW# Saturday Default: Default: Selection: Yes or No Selection: Yes or No This prompt, and the next six day of the week UW# Group Enable prompts, select the days of the week that the User Group Window is active.
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 104 Each sked number can be programmed with one of Holiday Indexes for User Group Windows S## Function Code 24 functions for the . A function You can enable up to four Holiday Indexes to use is executed.
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 105 S## Function Code Enter the function code you want this sked to execute. Sked Function 12 is reserved and is not a valid entry. The programmer automatically displays the available parameter choices and range fields for this function (such as, Yes/No is automatically displayed for the areas when choosing the Arm/Disarm function while a blank prompt exists for the point number you want to bypass when choosing the Bypass Point function).
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 106 Unbypass All Points: This function is Unbypass all S## Area 1[through 8] not available as a command center points in Area #. S## Area # function. The entry in the...
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 107 Test Report: This function emulates Defer the Test S## Defer Test the Send Report? command center Report. function. This function generates a Test Default: No Send the Test Report ONLY from Area 1 but contains...
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 108 Execute Custom Func: This function Blank (0) No command center S## Cmd Center emulates any of the custom functions is specified for assigned to the command center that Default: Blank (0)
This affects all doors that this user is assigned to with this specific authority level. The D9412G supports eight doors; the D7412G supports two doors. 0101 To regulate a user’s access for certain doors, assign the user a different authority level # with the same 0101 authority functions enabled.
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 110 Secure Door: This function Secure Door #. S## Door 1 [through 8] emulates the SECURE? 12345678 Default: No command center function for securing a door. Selection: Yes or No...
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 111 No Entry Events Off: The control Enable the reporting S## Door 1 [through 8] panel can log No Entry Events of No Entry Events Default: No when an invalid token is detected for Door #.
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 112 Exceptions: S## Time To prevent the sked from activating on certain days Default: 00:00 Xept Holiday of the year, program Yes, and enable Xept Holiday at least one Holiday Index. When...
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 113 Holiday Indexes S## Xept Holiday This programming module has two sections: Default: Add/Change/Delete and View Holidays. Use the Selection: Yes or No Add/Change/Delete section to program the Holiday Indexes. The View Holidays section is a view-only Prevent this sked from operating on section provided for your convenience.
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 114 Holiday Index 1 Default: Selection: Yes or No Use this date in Holiday Index 1. Do not use this date in Holiday Index Holiday Index 2 Default: Selection: Yes or No...
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 115 SDI Automation 6.0 RADXAUX1 Define the characteristics of the D9133 Serial Interface Module when used with Home or Business Introduction Automation software. The D9133 Serial Interface The RADXAUX1 Handler is primarily used for...
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 116 9133 Supervision Status Rate Default: Default: Selection: Yes or No Selection: 0 to 255 Supervise the D9133 Serial Interface Status information is only sent when Module. requested. Do not supervise the D9133 Serial...
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 117 connected to a D9133DC Direct Connect 6.4.1 User Interface Modifications for Programming Module. COMMAND 43 • Provide for local programming by a D9133 COMMAND 43 was modified to compensate for the Serial Interface Module.
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 118 This prompt and the next three prompts determine When configuring this item to allow for the IP address for RPS. local programming, the D9133 needs Jumper 8 shorted, power must be cycled An IP address consists of four fields.
Page 119
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 119 For Best Data Smart One V.92: Both the U.S.Robotics V.92 56 K Modem Type [A][T][S][3][7][=][9][Enter] (model # 5686, includes V.92 and V.90 For US Robotics: 56 K standard technology) and the Best Type [A][T][&][N][6][Enter].
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 120 Figure 7: Com Port Selection within HyperTerminal Figure 8: External Modem Connection D9133DC 1 2 4 8 SE RR XTXR XT XBU S 1 - RPS Remote Account Manager...
Page 121
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 121 In order to use an off-the-shelf external modem and a D9133DC serial module to connect to the control panel using RAM, use the following settings: 1. RADXAUX1\ENHANCED COMM\Enhanced Comm\No 2.
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 122 Enable Ext Modem RAM Line Monitor Default: Default: Selection: Yes or No Selection: Yes or No Enable SDI Address 88 for use with an This item is not yet implemented. Keep this item set external modem.
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 123 This prompt and the next three determine the IP Enhanced Comm addresses for each of the four paths available when using the D5200. Default: An IP address consists of four fields. Each field has a...
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 124 This prompt and the next two prompts determine Each time the SDI Path sends this Heartbeat Event, how the SDI Path is supervised between the SDI it expects an acknowledgement within the amount of Path # Ack Wait device and the central station(s).
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 125 Once the control panel receives acknowledgement The value entered for Path # Ack Wait from the central station, the control panel returns to Tone must not equal the time out entry...
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 126 Parity/Stop This item must be set to On when using Default: No/1 the External Modem feature. Selection: No/1, No/2, Odd/1, Even/1 9133 Supervision No/1 No parity, 1 stop bit.
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 127 RG# 1 Attempt Enable Anti Replay Default: Default: Selection: Yes or No Selection: Yes or No This route group attempts the primary This feature is used primarily for two purposes:...
Cross Point Groups were established in the D9412G and D7412G to support the Cross Point functions. There are 31 Cross Point Groups in the D9412G and ten in the D7412G. Each Cross Point Group consists of eight points and is identified by the point numbers in them (for example, Cross Points 1 to 8, Cross Points 9 to 16, and so on).
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 129 Conversely, if a single Cross Point detects an alarm, then restores, and no other conditions occur, an Unverified Event is generated for that point. A second alarm on the first point does not create an Alarm Event but rather an Unverified Event.
Page 130
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 130 Notes Bosch Security Systems | 10/03 | 47775E...
D9412G/D7412G | Program Entry Guide | 7.0 RADXAXS EN | 131 D#CC#Scope 7.0 RADXAXS Default: Blank Door Profile Selection: Blank, 1 to 8 This programming category is used to: 1 to 8 Determines disarming rights. The • Assign an area, that also activates the D9210B user’s access level in conjunction with...
D9412G/D7412G | Program Entry Guide | 7.0 RADXAXS EN | 132 D# Interlock Point Doors that are activated by Fire Unlock must be returned to normal using the Door Default: Blank Control function on the control center. Selection: Blank, 1 to 127, 129 to 247...
D9412G/D7412G | Program Entry Guide | 7.0 RADXAXS EN | 133 D# Buzz Time D# Card Type Default: 2 seconds Default: Selection: Blank, 1 second to 240 seconds Selection: 0 to 3 Blank Buzz Time is not programmed for this Card format is 26-bit Wiegand.
D9412G/D7412G | Program Entry Guide | 7.0 RADXAXS EN | 134 Use this program item to disable the strike, but still D# Deact On Open? activate the programmed shunt time upon a REX an area. Default: Use this parameter when a user can open...
D9412G/D7412G | Program Entry Guide | 7.0 RADXAXS EN | 135 D# Enter Request? D# Access Granted? Default: Default: Selection: Yes or No Selection: Yes or No A Door RTE Event from this door Access Events from this door controller...
Page 137
D9412G/D7412G | Program Entry Guide | Programming Prompts Directory EN | 137 CC# Assign Door........49 Area Parameters...........34 CC# Trouble Tone .........49 Area Parameters ..........34 CC# Entry Tone........49 Area............34 CC# Exit Tone ........49 A# Area On ..........34 CC# Arm Now Warn ......50 Error! Reference source not found.Error!
Page 138
D9412G/D7412G | Program Entry Guide | Programming Prompts Directory EN | 138 User Cmd 7..........57 L## User Cmd 7 ........63 User Cmd 9..........57 L## User Cmd 9 ........64 Bypass a Pt ..........57 L## Bypass a Pt........64 Unbypass a Pt ..........57 L## Unbypass a Pt .........64...
Page 139
D9412G/D7412G | Program Entry Guide | Programming Prompts Directory EN | 139 P## Local While Armed ......86 Panel-Wide Relays .........71 P## Disable Rst........87 AC Failure ..........71 P## FA Retrnable ........87 Battery Trouble........71 P## BP Retrnable ........87 Phone Fail..........71 P## Bypassable ........88 Comm Fail..........72...
Page 140
D9412G/D7412G | Program Entry Guide | Programming Prompts Directory EN | 140 W# Close Window Start ......99 S## Cmd Center 1[through 8] ..109 W# Close Window Stop......99 S## Access Ctl Level #....109 W# Xept Holiday........100 S## Access Ctl Level#....109 W# Holiday 1 ........100 S## Door 1 [through 8]....109...
Page 141
D9412G/D7412G | Program Entry Guide | Programming Prompts Directory EN | 141 9133 Supervision ........126 RADXAUX1............115 Base Port Number .........126 SDI Automation..........115 Route Group Attempts ........126 Enable SDI Auto ........115 RG# 1 Attempt........127 Baud Rate ..........115 Miscellaneous ..........127 Parity/Stop..........115 Fire Supv Res Type .......127 9133 Supervision ........116...