D9412GV4/D7412GV4/D7212GV4
L## Remote Program
Default:
Selection:
Function No.
29
Start a remote programming software (RPS) session when the phone rings at the control
panel.
L## Move to Area
Default:
Selection:
Function No.
30
Temporarily switch to a different area and perform keypad functions related to that area.
L## Display Rev
Default:
Selection:
Function No.
32
Display the control panel model name and software revision. For example:
L## Service Walk
Default:
Selection:
Function No.
33
Start a Service Walk Test for all 24-hour Interior or Perimeter Controlled points in the control
panel.
Points are not included in this test if:
When a Service Walk Test is initiated, one person can test all the points in the control panel
without assistance. The following features are provided with the Service Test Mode:
Bosch Security Systems, Inc.
Authority Levels 1-4, 15: Enabled (E)Authority Levels 5-14: Blank (-)
- or E
Function Name
Remote Programming [COMMAND][4][3]
Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
- or E
Function Name
Move to Area
Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
- or E
Function Name
Display Software
Revision
9412GV4 REV ##.##
Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
- or E
Function Name
Service Walk test
Points are in an area that is already in a Walk Test Mode.
Points are assigned to an area that is not enabled A# Area On.
Points are in an area that is Master or Perimeter armed.
Point source is Unassigned and the Point Index is set to 0.
Display indicates exactly how many points can be tested.
Battery and bell tests do not occur during this Walk Test.
The test ends when all points are tested or the test times out after 20 min of inactivity.
Events print locally without alarm annunciation or reporting to the central station
receiver.
D1255 Keypad displays a sequential count and the text for the point after each point is
activated and restored.
The D1255 Keypad displays ALL PNTS TESTED.
If enabled in Routing, Service Start and Service End are reported at the central station
receiver for the beginning and end of the test.
Program Entry Guide
Panel and Area Wide Parameters | en 111
Alternate Keystroke
Alternate Keystroke
[COMMAND][5][0]
Alternate Keystroke
[COMMAND][5][9]
Alternate Keystroke
(Menu function only)