146 en | Points
5.3

Point Assignments

These entries assign point indexes to Points 1 to 127, 129 to 247 for the D9412GV4, Points 1
to 75 for the D7412GV4, Points 1 to 40 for the D7212GV4, and assign the points to the areas.
Also included in this section are parameters used to set the point's debounce count, Relay
(for assigning relays to follow alarms for a group of points), and custom keypad and report
text for each point.
P### Point Source
Default:
Selection:
Unassigned
Zonex
Octo-input
Wireless
Onboard
Door Point
NOTICE!
The Door Point option for P## Point Source is not selectable from the Point Assignment menu.
To select Door Point option, set the point assignment number in ACCESS CONTROL > Door,
Strke, and Event Profiles > D# Door Point.
NOTICE!
Point number 128 is reserved for supervising Zonex 1.
Point number 248 is reserved for supervising Zonex 2 (D9412GV4).
P### Point Index
Default:
Selection:
This entry selects one of the 31 Point Index codes that define the point's characteristics and
determines how the control panel responds to various point conditions.
A setting of 0 disables the point.
Missing Point Report
If a Point Index is assigned to a point that has an incorrect address or that is not connected to
the point bus, a Missing Point Report occurs.
When a POPIT is missing, the control panel generates the following responses based on the
point type:
POPIT modules monitor their sensor loops for three conditions: loop normal, loop open, and
loop shorted. They send reports on these three conditions to the control panel. The control
panel uses point programming to interpret the sensor loop information sent by the POPITs
and to make the appropriate system response.
F.01U.218.312 | 04 | 2012.03
On-Board for Points 1 to 8, Wireless for point 9
Unassigned for all other points
Unassigned, Zonex, Octo-input, Wireless, On-Board, Door Point
Point is not installed.
Point is installed on a Zonex bus input module. Including Zonex RF
point.
Point is installed on an SDI2 bus input module.
Point is installed on an SDI2 bus RF receiver.
Point is installed on control panel.
Point is installed on a SDI bus Door Controller. Not selectable here.
Refer to the program record sheet
0 to 31
Fire points generate missing trouble responses.
Non-fire 24-hour points generate missing alarm responses.
Non-fire, non 24-hour points generate missing alarm responses while armed, and trouble
responses while disarmed. Exception: Non-fire, non-24-hour points with a point response
of 9 to D generate a missing alarm response while disarmed.
Program Entry Guide
D9412GV4/D7412GV4/D7212GV4
Bosch Security Systems, Inc.