Bosch D9412GV4 Program Entry Manual page 171

Table of Contents

Advertisement

D9412GV4/D7412GV4/D7212GV4
24
No Entry Events Off: (D9412GV4 and
D7412GV4) The control panel can log No
Entry Events when an invalid token is
detected for a specific door. No Entry Events
include No Entry-Secured, No Entry-Interlock,
No Entry-Unknown ID, and No Entry-Level.
These events can be directed to print at a
local printer or send a report remotely
through phone routing. This sked disables No
Entry Events to be reported for Door #.
28
Expanded Off-Normal Test Report: To generate this event, one or more points must be in an off-normal state
at the time the sked executes. In addition, any system trouble that is active also generates an Expanded Off-
Normal Test Report. Expanded Off-Normal Test Reports include the Off Normal Test Report Event as well as
the supplementary event at the time the report is generated.
The Event Log shows only a Test Report Event.
If none of these conditions exists at the time the sked executes, only a Sked Executed Event is generated and
the Off-Normal Test Report is not sent.
29
Non-Expanded Off-Normal Test Report: Non-Expanded Off-Normal Test Report Events are only sent when any
point is in the off-normal state from any area, but only sends the Off Normal Test Report Event. Any system
trouble that is active also generates a Non-Expanded Off-Normal Test Report.
The Event Log only shows a Test Report Event.
If none of these conditions exist at the time the sked executes, only a Sked Executed Event is generated and
the Non-Expanded Off-Normal Test Report is not sent.
Table 6.2
NOTICE!
To meet UL 864 daily Test Report requirements (when using two phone lines) (D9412GV4 and
D7412GV4), you must still use Sked Function Code 9, Test Report and program it to occur on
a daily basis as per AHJ requirements.
S## Time
Default:
Selection:
Enter the time that the sked executes. Make entries using a 24-hour clock (for example, 7:00
AM is entered as 07:00, 2:45 PM is entered as 14:45).
Disabled skeds can have their time set to Disabled; however, to ensure that a sked is fully
disabled, enter [COMMAND][5][2] (Change Skeds function) and select DISABLE?
S## Date
Default:
Selection:
Enter the date that the sked executes.
Disabled skeds have their date set to Disabled. If you receive from the control panel and the
entry for this prompt is Disabled, but dates were programmed before, the sked can be
disabled from the keypad using the Change Skeds function.
S## Sunday
Default:
Selection:
Yes
No
Bosch Security Systems, Inc.
S## Door 1 [through 8]
Default: No
Selection: Yes or No
This parameter enables
the sending of No Entry
Events for Door #.
00:00
HH:MM (hours and minutes)
__/__
MM/DD (month and date)
No
Yes or No
Activate this sked on Sundays.
Do not activate this sked on Sundays.
Program Entry Guide
Schedules (Skeds) | en 171
Yes
Enable the reporting of
No Entry Events for Door
#.
No
Do not enable the
reporting of No Entry
Events for Door #.
F.01U.218.312 | 04 | 2012.03