Bosch D9412GV4 Program Entry Manual page 119

Table of Contents

Advertisement

D9412GV4/D7412GV4/D7212GV4
NOTICE!
Fire Time and Fire Pattern must be programmed in Bell Parameters. This relay activates
according to the bell pattern and remains active until the bell time expires. P## Silent Bell
must be No in order for the bell to ring upon alarm.
NOTICE!
Although Relay C is a valid entry for A# Fire Bell, do not program Relay C for this entry. Use
Relay A for the A# Fire Bell.
NOTICE!
To meet UL 864 requirements, set A# Fire Bell to a value other than 0.
A# Reset Sensors
Default:
Selection:
Unlike the default relay for Alarm Bell and Fire Bell, this voltage-output relay (Relay C) de-
activates for 5 sec when the Reset Sensors? function is activated from the keypad or during a
Fire Walk Test.
NOTICE!
The Reset Sensors time converts from the 5 sec default time to the time programmed in A#
Verify Time (Section 3.10 Area Parameters, page 61) when a point programmed for P## Alarm
Verify (Section 5.1 Point Index, page 130) enters an alarm condition.
NOTICE!
When sharing one relay to reset sensors in two or more areas, you must program the
following. Failure to do so causes TROUBLE PT ### for all point types programmed as P##
Resettable.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set A# Reset Sensors to a value
other than 0.
A# Fail to Close
Default:
Selection:
This relay activates when the Closing Window expires for the specified area. It remains active
until midnight, another Closing Window starts, or the control panel resets, whichever occurs
Bosch Security Systems, Inc.
C
0, 1 to 128, A, B, C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
CC # Scope must include all areas that share the relay.
L## Reset Sensors authority must be assigned to the passcode that activates the
COMMAND 47 or Reset Sensor function.
A# Verify Time must be the same number of seconds for all areas that share the relay.
0
0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Program Entry Guide
Panel and Area Wide Parameters | en 119
F.01U.218.312 | 04 | 2012.03