6: Control Module Delay Timer; Walktest; Read Status; 1=System Point - Honeywell Fire-Lite Alarms ES-200X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-200X:
Table of Contents

Advertisement

Operating Instructions
4.22.6 Control Module Delay Timer
The control module delay feature, if enabled, will delay activation of a control module after a programmed time of 1-180 seconds after
being triggered by an alarm condition. This feature requires the approval of the local Authority Having Jurisdiction. See the table on
page 49 for allowable settings.

4.23 Walktest

Walktest is a feature which allows one person to test the fire alarm system. An audible walktest will momentarily sound the Notification
Appliance Circuits in the building and store the walktest information in a file at the panel. A silent walktest will not sound the NACs but
will store the walktest information in a file which can be viewed at the panel. Disabled NAC devices will not activate during walktest.
Alarm/Shorted Condition
When in audible Walktest, the panel responds to each new alarm and activates its programmed control outputs for four seconds, if those
outputs have been programmed for silenceable activation. It also stores each alarm in the walktest history file which can be sent to an
optional printer. The stored display will be the same as if the device actually activated except the colon (:) in the time stamp is replaced
with an asterisk (*).
Note that if the system under test includes one or more enabled monitor modules, the following may apply:
If the monitor module is used for a supervised, 2-wire smoke zone, alarming any monitor module in the system will result in the
activation of programmed control outputs for an additional eight seconds or less. This is caused by the temporary removal of 24
VDC resettable power from the monitor module. The monitor module reports this loss of power as an open condition in addition to
the alarm condition.
Open Condition
Addressable devices are monitored for fault conditions during Walktest mode. When a new trouble condition occurs, the FACP will acti-
vate all NACs and control modules programmed for Walktest and mapped to the faulty device, then shut them off after eight seconds.
While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of the Program and status change opera-
tions). The alarm relay is not activated.

4.24 Read Status

Read Status functions do not require a password. The control panel will continue to provide fire protection while in Read Status mode.
This mode can be entered while the control panel is in alarm or trouble. If a new alarm or trouble occurs during these functions, the Read
Status is exited to prevent confusion.
Read Status Entry
When the operator presses the control panel
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status mode which allows the user to view
and print the programmed features and status of the control panel.
The following screens will be displayed:

1=SYSTEM POINT

2=ZONES
Read Status Screen #1
1=ANNUNCIATORS
2=COMMUNICATOR
Read Status Screen #4
4.24.1 System Point
READ STATUS
1=SYSTEM POINT
2=ZONES
Read Status Screen #1
114
ENTER
READ STATUS
READ STATUS
Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed:
key, the LCD will display the following:
1=READ STATUS MODE
2=PROGRAMMING MODE
3=FSTOOL UP/DOWNLOAD
4=USB UP/DOWNLOAD
READ STATUS
1=TROUBLE REMINDER
2=TIMERS
3=NACS
Read Status Screen #2
READ STATUS
1=FUTURE USE
2=PRINT
3=TIME/DATE
Read Status Screen #5
READ SYSTEM POINT
SELECT TYPE
1=DETECTOR
2=MODULE
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
READ STATUS
1=RELAYS
2=PROGRAM CHECK
3=HISTORY
Read Status Screen #3
READ STATUS
CHARGER ENAB
YES
4XTM SPV ENAB
NO
REM SYNC ENAB
YES
Read Status Screen #6
Walktest