Read Status; 1=Input Zones; 2=Nac 2 - Honeywell GF505 Manual

Fire alarm control panels
Table of Contents

Advertisement

Operating Instructions
While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of the Program and status change opera-
tions). The alarm relay is not activated.
NOTE: In Walktest, a NAC open or short fault will not cause the NACs to activate.

4.19 Read Status

Read Status functions do not require a password. The control panel will continue to provide fire protection while in Read Status mode.
This mode can be entered while the control panel is in alarm or trouble. If a new alarm or trouble occurs during these functions, the Read
Status is exited to prevent confusion.
Read Status Entry
When the operator presses the control panel Enter key, the LCD will display the following:
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status mode which allows the user to view
and print the programmed features and status of the control panel.
The following screens will be displayed:
READ STATUS

1=INPUT ZONES

2=NACS
3=RELAYS
Read Status Screen #1
4.19.1 Input Zones
READ STATUS
1=INPUT ZONES
2=NACS
3=RELAYS
Read Status Screen #1
Pressing the down arrow key will allow the selection of Zones 4-5 for the GF505 and Zones 4-10 for the GF510.
The operator selects the zone which is to be viewed by pressing the number corresponding to the desired zone in each screen. For exam-
ple, if 1 is pressed, the display will change to a screen similar to the following:
Pressing the down arrow key, while viewing the screen shown above, will allow the operator to view additional programming informa-
tion about the selected device, such as:
Enable/Disable Status
Device Type
Alarm Verification On/Off (for detectors)
PAS (Positive Alarm Sequence) Yes/No (for detectors only)
Pre-Signal Yes/No (for detectors only)
Input Zone Freeze Supervision
Adjective/Noun descriptor
ACC Message
Description
4.19.2 NAC
Pressing 2 while viewing Read Status Screen #1 will display the following screen:
92
1=READ STATUS MODE
2=PROGRAMMING MODE
3=FUTURE USE
4=REMOTE DOWNLOAD
READ STATUS
1=SYSTEM SETTINGS
2=TIMERS
3=DAYLIGHT SAVINGS
Read Status Screen #2
Pressing 1 while viewing Read Status Screen #1 will cause the following screens to be displayed:
INPUT ZONES
1=ZONE 1
2=ZONE 2
3=ZONE 3
PULL STATION
ZONE 1
PRESS
NAC STATUS
1=NAC 1

2=NAC 2

READ STATUS
1=HISTORY
2=PRINTER
3=ANN-BUS
Read Status Screen #3
TO VIEW
3=NAC 3
4=NAC 4
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
Read Status
READ STATUS
1=CENTRAL STATION
2=PHONE LINES
3=SERVICE TERMINAL
Read Status Screen #4