4.2 Indication of Direction of the Rotating Field,
or Direction of Rotation without Connecting
Test Leads
1.
Do not connect any test leads to the instrument.
2.
Position the instrument on the motor, within 2.5 cm, parallel to
the shaft in the direction indicated by the symbol on the front
panel.
3.
Press the ON (TEST) button. The Green LED indicator indi-
cates that the instrument is in operation.
4.
The clockwise or counter-clockwise rotation indicator lights to
indicate the direction of the rotating field.
Note: The instrument does not work on motors controlled by
frequency converters.
The table below summarizes the conditions necessary to obtaining
a reliable test result.
Number of rotations of the
rotating field (per minute) as a
Number of
function of frequency (Hz)
pairs of poles
16 2/3
1
1000
2
500
3
333
4
250
5
200
6
167
8
125
10
100
12
83
16
62
10
50
60
3000
3600
1500
1800
1000
1200
750
900
600
720
500
600
375
450
300
360
250
300
188
225
Phase & Motor Rotation Tester Model 6609
R
Angle
Minimum Ø of the
between
poles
0
60
30
20
15
12
10
7.5
6
5
3.75
motor casing
cm
5.3
10.7
16.0
21.4
26.7
32.1
42.8
53.5
64.2
85.6