Tuning Menu - Watts Aerco Innovation 800 User Manual

Gas-fired hot water boilers
Table of Contents

Advertisement

Innovation Hot Water Hot Water Boiler User Manual
Menu Item Display
25
IGST Version
26
IGN Timing Setting
* DO NOT CHANGE the Analog Output menu item from its Default
setting (Valve Position 0-10V).

3.7 TUNING MENU

The Tuning menu items in Table 3-5 are Factory set for each individual unit. Do not change
these menu entries unless specifically requested to do so by factory-trained personnel.
A full description of each item appears in Table A-4 of Appendix A – Innovation Menu Item
Descriptions.
Menu Item Display
1
Prop Band
2
Integral Gain
3
Derivative Time
4
Warmup Prop Band
5
Warmup Int Gain
6
Warmup PID timer
7
Min Load Adj (an offset)
8
Max Load Adj (an offset)
9
FFWD Temp
10
Outlet Feedback
11
Feedback Gain
Breakpoints – shown only if the Heatr Bkpt Dsp option in the Calibration Menu is Enabled (see
section 3-8). The Breakpoint values correspond to a 130°F default setpoint
12
Breakpt at 100%
13
Breakpt at 90%
14
Breakpt at 80%
15
Breakpt at 70%
16
Breakpt at 60%
17
Breakpt at 50%
18
Breakpt at 40%
Page 42 of 174
11/15/2016
CHAPTER 3 – OPERATION
Available Choices or Limits
Minimum
V2.00 or Lower
4 Sec
--CAUTION -
Table 3-5. Tuning Menu
Available Choices or Limits
Minimum
1°F (-17.2°C)
0.00
0.00 min
1°F (-17.2°C)
.00
0 sec.
-50°F (-27.5°C)
-50°F (-27.5°C)
30°F (-1.1°C)
Yes (On) or No (Off)
0.01
30°F (-1.1°C)
30°F (-1.1°C)
30°F (-1.1°C)
30°F (-1.1°C)
30°F (-1.1°C)
30°F (-1.1°C)
30°F (-1.1°C)
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
- INTERNATIONAL
Maximum
V2.02
7 Sec
Maximum
200°F (93.3°C)
30°F (-1.1°C)
10.00
2.00 min
120°F (48.9°C)
2.00
240 sec.
+50°F (27.5°C)
+50°F (27.5°C)
245°F (118.3°C)
Read Only Value
1.00
240°F (115.6°C)
85°F (29.4°C)
240°F (115.6°C)
240°F (115.6°C)
87°F (30.5°C)
240°F (115.6°C)
88°F (31.1°C)
240°F (115.6°C)
89°F (31.7°C)
240°F (115.6°C)
90°F (32.2°C)
240°F (115.6°C)
94°F (34.4°C)
Default
0
-
Default
3.00
0.20 min
95 °F (35°C)
0.50
20 sec.
0°F (0°C)
0°F (0°C)
Yes (On)
0.10
86°F (30°C)
OMM-0120_0A
GF-128-I

Advertisement

Table of Contents
loading

Table of Contents