Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 2: OPERATION

2.3 MENU STRUCTURE

The Main Menu give you access to all Edge [i] Controller user functionality. There are four major
divisions within the menu structure.

Unit Status Menu

2.3.1
The Unit Status menu contains the following sections and parameters. Unlike other Edge
menus, navigation starts at the Unit Status screen and proceeds from there by scrolling right.
Main Menu → Unit Status
Target Fire Rate
Current Fire Rate
Flame Strength
Inlet Temp
Setpoint
Outlet
Air Inlet
O2
Exhaust
Main Menu → Plant Status – BST Manager Only
Outside Temp
SH/Other Setpoint
SH/Other Supply
Inlet Temp
Units Available
Units Firing
Units Online
SH/Other Fire Rate
Main Menu → BST Cascade Status – BST Manager Only
SH/Other Fire Rate
Units Online
SH/Other Setpoint
Units Available
Sh/Other Supply
OMM-0145_A99 • GF-218 •
Figure 3.3: The Edge [i] Controller Main Menu
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
9/18/2019
The target Fire Rate (0% to 100%).
The current Fire Rate (0% to 100%).
The current Flame Strength (0% to 100%).
The current Inlet Water temperature
The unit's current Setpoint.
The current Outlet temperature.
The current Air Inlet temperature.
The Current O
reading.
2
The current Exhaust temperature.
The reading of the outside temperature meter
The BST cascade's current Setpoint.
The supply temperature reading.
The inlet temperature reading.
The number of units in the BST cascade.
The number of units in the BST cascade firing.
The number of units in the BST cascade online.
The fire rate for the BST cascade.
The fire rate for the BST cascade.
The number of units in the BST cascade online.
The BST cascade's current Setpoint.
The number of units in the BST cascade available.
The supply temperature reading.
Page 15 of 157