Watts Aerco Innovation 800 User Manual page 41

Gas-fired hot water boilers
Table of Contents

Advertisement

Innovation Hot Water Hot Water Boiler User Manual
Menu Item Display
1
Internal Setpt
2
Unit Type
3
Unit Size
4
Fuel Type
5
Hot Water Boiler Mode
Remote Signal
6
(If Mode = Remote Setpoint,
Direct Drive or Combination)
7
Outdoor Sensor
System Start Tmp
8
(If Outdoor Sensor =Enabled)
Setpt Lo Limit
9
10
Setpt Hi Limit
11
Temp Hi Limit
12
Max Valve Position
Pump Delay Timer
13
14
Aux Start On Dly
15
Failsafe Mode
16
* Analog Output
17
Low Fire Timer
18
Setpt Limiting
19
Setpt Limit Band
Network Timeout
20
21
Shutoff Dly Temp
22
Demand Offset
23
Deadband High
24
Deadband Low
OMM-0120_0A
GF-128-I
CHAPTER 3 – OPERATION
Table 3-4. Configuration Menu
Available Choices or Limits
Minimum
Lo Temp Limit
800, 1060, 1350 MBH
(175.8, 234.5, 310.7, 395.6 kW)
Natural Gas, Propane
PWM Input (Legacy BMS),
Enabled or Disabled
30°F (-1.1°C)
40°F (4.4°C)
Setpt Lo Limit
40°F (4.4°C)
40%
0 min.
0 sec.
Shutdown or Constant Setpt
Off, Setpoint, Outlet Temp, Valve Pos
4-20mA, valve Pos 0-10v
2 sec.
Enabled or Disabled
0°F (0°C)
5 Sec
0
0
0
0
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
- INTERNATIONAL
Maximum
Hi Temp Limit
Innovation WH
Constant Setpoint,
Remote Setpoint,
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
Network
100°F (37.8°C)
Setpt Hi Limit
190°F (87.8°C)
200°F (93.3°C)
100%
30 min.
120 sec.
600 sec.
10°F (5.5°C)
999 Sec
25
25
25
25
Default
130°F (54.4°C)
Innovation WH
800, 1060 or 1350
MBH
Natural Gas
Constant Setpoint
4 – 20 mA,
1-5V
Disabled
60°F (15.5°C)
60°F (15.5°C)
150°F (65.6°C)
160°F (71.1°C)
100%
0 min.
0 sec.
Shutdown
Valve Pos 0-10v
2 sec.
Disabled
0
30 Sec
8
5
0
0
Page 41 of 174
11/15/2016