APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS
Table A-3: Configuration Menu Item Descriptions
Table A-3: CONFIGURATION MENU ITEM DESCRIPTIONS
See section 3-6 for a range of choices and the default values.
MENU LEVEL & OPTION
1
Internal Setpoint
2
Unit Type
3
Unit Size
4
Fuel Type
5
Heater Mode
6
Remote Signal
7
Outdoor Sensor
8
System Start Tmp
9
Setpoint Lo Limit
10
Setpoint Hi Limit
11
Temp Hi Limit
12
Max Valve Position
13
Pump Delay Timer
14
Aux Start On Dly
15
Failsafe Mode
16
Analog Output
17
Lo Fire Timer
18
Setpt Limiting
19
Setpt Limit Band
OMM-0120_0A
GF-128-I
Allows internal setpoint to be set.
Innovation Hot Water Boiler
800 MBH (234.5 kW), 1060 MBH (310.7 kW) or 1350 MBH
(395.6 kW)
Allows selection of Natural Gas or Propane.
It allows selection of: Constant Setpoint, or Remote Setpoint.
Used to set the type of external signal which will be used
when operating in the Remote Setpoint mode.
Allows outdoor sensor function to be enabled or disabled.
In Outdoor Reset mode, the temperature above which the
unit shuts down.
Used to set the minimum allowable setpoint, 40°F (4.4°C) to
Setpoint Hi Limit.
Used to set the maximum allowable setpoint (Setpoint Lo
Limit to 190°F (87.8°C).
This is the maximum allowable outlet temperature (40 to
200°F (93.3°C). Any temperature above this setting will turn
off the unit. The temperature must then drop 5°F (2.75°C)
below this setting to allow the unit to run.
Sets the maximum allowable valve position for the unit (40%
to 100%).
Specifies the amount of time (0 to 30 min.) to keep the pump
running after the unit turns off.
Specifies the amount of time to wait (0 to 120 sec.) between
activating the Aux Relay (due to a demand) and checking the
pre-purge string to start the heater.
Allows the Failsafe mode to be set to either Constant
Setpoint or Shutdown.
Must be set to Valve Pos 0-10 V.
Specifies how long (2 to 600 sec.) to remain in the low fire
position after ignition, before going to the desired output
N/A for Hot Water Boilers
N/A for Hot Water Boilers