Watts Aerco Innovation 800 User Manual page 112

Gas-fired hot water boilers
Table of Contents

Advertisement

Innovation Hot Water Hot Water Boiler User Manual
Menu Item Display
SN
1.
WHM Mode
2.
WHM Setpoint
3.
WHM Nxt On VP
4.
WHM Nxt Off VP
5.
Lead/Lag Hours
6.
WHM Upld Timer
7.
Setpoint Setback
8.
Setback Setpoint
9.
Setback Start
10.
Setback End
11.
WHM Auto Mstr *
12.
WHM Auto Timer *
13.
WHM min addr
14.
WHM max addr
15.
SSD address
16.
SSD Temp Format
17.
1 Valve Status 8
18.
1 Comm Errors 8
19.
WHM On Delay
20.
WHM Off Delay
21.
Over WHM Under
22.
WHM Min Units
23.
WHM Warmup Time
24.
WHM On Timeout
25.
WHM Valve State
26.
Valve Override
27.
Valve Feedback
28.
Valve Fdbk timer
29.
ValveFdbk Status
30.
MB Head Temp En
31.
WHM Header Temp
Page 112 of 174
11/15/2016
CHAPTER 8 – WATER HEATER MANAGEMENT
Table 8-1. WHM Menu
Available Choices or Limits
Minimum
40°F (4.4°C)
16%
16%
25
0
40°F (4.4°C)
12:00am
12:00am
10 sec.
1
1
0
Degrees or Points
0
0
30 sec
30 sec
0
1
0
15 Sec
0
Auto, Open or Closed
Enable or Disable
30 sec
Close
Enable or Disable
0
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
Maximum
Off, WHM Slave,
WHM Master
190°F (87.8°C)
100%
100%
225
9999
Enable, Disable
150°F (65.5°C)
11:59pm
11:59pm
Yes or No
120 sec.
8
8
250
0
0
300 sec
300 sec
0
8
300 sec
300 Sec
1
240 sec
Open
0
- INTERNATIONAL
Default
Off
130°F (54.4°C)
60%
30%
72
0
Disable
130°F (54.4°C)
12:00am
12:00am
No
30 sec.
1
8
0
Degrees
0
0
60 sec
60 sec
0
1
30 sec
30 Sec
0
Auto
Disable
60 sec
Fdbk state
Disable
Header Temp
OMM-0120_0A
GF-128-I

Advertisement

Table of Contents
loading

Table of Contents