Innovation Hot Water Hot Water Boiler User Manual
APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS
Table A-4: Tuning Menu Item Descriptions
Table A-4: TUNING MENU ITEM DESCRIPTIONS
See section 3-7 for a range of choices and the default values.
MENU LEVEL & OPTION
Prop Band
1
Integral Gain
2
Derivative Time
3
Warmup
4
Warmup Prop Band
5
Warmup Int Gain
6
Warmup PID Timer
Min Load Adj
7
Max Load Adj
8
FFWD Temp
9
Outlet Feedback
10
Feedback Gain
11
Breakpoint at 100%
12
Thru
Thru
22
Breakpoint at 0%
OMM-0120_0A
GF-128-I
Generates a valve position based on the error that exists between
the setpoint temperature and the actual outlet temperature. If the
actual error is less than the proportional band setting (1 to 120°F,
-17.2 to 48.9 °C), the valve position will be less than 100%. If the
error is equal to or greater than the proportional band setting, the
valve position will be 8%.
This sets the fraction of the output, due to setpoint error, to add or
subtract from the output each minute to move towards the
setpoint. Gain is adjustable from 0.00 to 10.00
This value (0.0 to 20.0 min.) responds to the rate of change of the
setpoint error. This is the time that this action advances the
output.
The feature embodied in the next three menu items eliminates
Temperature Overshoots during the "Warmup" period of a cold
ignition cycle on all boilers by temporarily modifying the PID Gain
parameter during warmup and for a period defined in the Tuning
Menu.
Range = 1 – 120°F (-17.9°C to 48.9°C)
Range = 0.00 – 2.00
Range = 0 - 240 seconds
Setting is adjustable from -50°F to +50°F. It adjusts the output by
adding an offset to the breakpoint chart at minimum flow. This is
used to fine tune Feed-Forward (FFWD) output at low flow levels.
Setting is adjustable from -50°F to +50°F (-45.5 to +10 °C). It
adjusts the output by changing the scaling of the breakpoint chart
at maximum flow.
Displays the Feed-Forward temperature.
Used to Enable or Disable feedback. Disable this function for
Feed-Forward control only.
Adjustable from 0.01 to 1.00 (See NOTE below)
Allows breakpoint temperature settings 30°F to 240°F (4.4°C to
115.6°C), to be entered for 100% to 0% in 10% increments.
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
- INTERNATIONAL
DESCRIPTION
Default = 95°F (35°C)
Default = 0.50
Default = 20 seconds
Page 131 of 174
11/15/2016